Page 295 - B6118-AEW-XX-XX-PP-A-0001_(P19)_Contractors Manual
P. 295
CONSTRUCT
C1.6 DT Booth
Drive thru booth window replacement now The open aperture must then be closed off in
forms part of the Experience of the Future scope a fully watertight manner finished internally and
of works; mandatory for McOpCo restaurants, externally to match the existing surrounding
recommended for Franchised restaurants. finishes including the line on which they sit.
Replacement booth windows must: Generally, the external finish will be brick slip or
- Be solid from floor level to cill level by utilising render for which the principal contractor must
an insulated spandrel panel achieve an adequate match through their
- Be glazed from cill level to 250mm below soffit own procurement channels. This external finish
level should be applied onto a rigid insulation board.
- Be glazed for the full width of the booth as The insulation board must be tightly butt jointed
identified on the site specific drawings to the existing surrounding insulation board and
- Be glazed the full extent of any returns / sides sealed between using and expanding foam
to the booth as identified on the site specific filler or a compressible foam joint. Generally,
drawings most brick slips have previously been supplied
- Contain a sliding service window to allow to McDonald’s by Euro-brick, contact details:
customer / crew interaction 01179 717 117, web site www.eurobrick.co.uk
although alternative suppliers are equally
Booth windows must be provided by the use of acceptable.
PPC alu shopfront framing as described under
the shopfront section. New booths must also be The rigid insulation board must be fully bonded
fitted with and mechanically fixed to a 18mm WBP plywood
backing board supported on a metsec metal
- Over window heaters, refer to services stud frame system tied into the existing walls.
specifications Internally, the metal stud should be finished with
- New ceiling a 12mm plywood and either a hygienic wall
- New lighting system finish or a further 9.5mm plasterboard
layer to which ceramic tiles can be applied.
Any existing booth windows which are being
removed or repositioned must be completed by Any replacement or remedial works to existing
the principal contractor. In such circumstances, booths with timber effect or grey cladding must
the existing (serv-o-slide) window must be be undertaken by Butterfield Signs.
carefully removed and disposed of as instructed
by the project manager (usually stored for future
use).
C1.6 DT Booths 4.0 25 July 2017