PVC strip curtains for the door should be included as standard.A F T




       The coldroom MUST incorporate an insulated and heated floor to avoid condensation problems
       causing future damage to the floor below.

        General                  Must comply with all relevant legislation in force at the time of manufacture.
        Temperature range        To be capable of maintaining the temperature in the range of 0 / +3 degrees
                                 Celsius.
        Dimensions               External dimensions as stated on project drawings.
        Insulation               80mm thick zero ODP injected polyurethane.
        Finishes                 External - white food safe laminate steel.
                                 Internal - white food safe laminate steel to walls and ceilings.

                            D R
        Floor                    The coldrom must have an insulated and heated floor to minimize the risk of
                                 condensation below.
        Door                     Hinged to suit clear opening of 0.750m x 1.920m high, with locking fastener and
                                 internal emergency release mechanism.
        NOTE: Although sliding doors are available, these are NOT recommended due to the tendency for them to repeatedly
        come off the runners as a result of rough handling by staff.

        Light                    The coldroom must be fitted with a suitable internal light and external switch, as
                                 standard. An emergency light to comply with BS5839 should be supplied and
                                 installed by the coldroom installer, in addition to the working light.
        Shelving                 Supply and install suitable 3 tier shelving, nominal size 1800 x 500mm, to fit under
                                 the internal evaporator
        Wall Spacers             Supply and install nom. 75mm x 75mm S/S top hat section spacers, to run the full
                                 length of all internal walls EXCEPT the wall under the evaporator.
        Equipment                Evaporator internally ceiling mounted. A condensate pump may be required
                                 and should be priced as an optional extra.
                                 External compressor unit in weather-proof housing and must be specified to be
                                 very quiet in operation to avoid nuisance to neighbours when running. ( Sylensys
                                 or similar)
        Controls                 filter/drier, sight glass etc.
                                 Suction line insulated with Armaflex insulation.
        Refrigerant              System to be leak checked, evacuated and charged with R134A refrigerant.
        Wiring                   Supplied from 20 amp single phase outlet provided by others.
        Pricing                  To  include  installation,  commissioning,  training,  provision  of  operation  and
                                 maintenance manual and shelving
        Warranty                 Twelve months parts and labour warranty should be required.