Health and Safety        Workplace health, safety and welfare
 Executive  3.3 Staff WC Provision





 ACOP   21    ■  the facilities should be fitted with doors at entrances and exits unless
          The  provisions  for  a  staff  WC  should  be  in
             other measures are taken to ensure an equivalent degree of privacy.
          accordance  with  Table  1,  Regulation  21  of
          Minimum numbers of facilities
          the  Workplace  (Health,  Safety  and  Welfare)
          197  Table 1 shows the minimum number of toilets and washbasins that
          Regulations  1992.  There  should  be  1No.  toilet
          should be provided where both men and women are working. Column 1 refers
          to the maximum number of workers likely to be in the workplace at any one
          provided as a minimum where there are up to
          time. If separate toilets are provided for a group of workers (eg men, women,
          office workers or manual workers), a separate calculation should be made for
          5No. members of staff on the premises at any
          each group. More facilities may be necessary if, for example, breaks are
          taken at set times or workers finish work together and need to wash before
          one time.
          leaving.
          Table 1 Number of facilities needed per number of people at work
           1               2               3 R A F T
                                           3
           Number of people    Number of cubicles  Number of washbasins
           at work
           1 to 5          1               1
           6 to 25         2               2
           26 to 50        3               3
           51 to 75        4               4
           76 to 100       5               5

 Guidance    21  198  Table 1 provides advice on provision for mixed workplaces. However, where it
          may be necessary to provide urinals for use by men, then the advice in Table 2 may
          be followed.
 ACOP   21  199  Table 2 may be followed as an alternative to column 2 of Table 1 if toilets
          are only used by men. A urinal may either be an individual urinal or a section
          of urinal space which is at least 600 mm long.
          Table 2 Number of facilities needed per number of men at work

           1               2
           Number of men   3D  Number of cubicles  Number of urinals
           at work
           1 to 15         1               1
           16 to 30        2               1
           31 to 45        2               2
           46 to 60        3               2
           61 to 75                        3
           76 to 90        4               3
           91 to 100       4               4