Page 76 - B8773-AEW-XX-XX-PP-A-0001_[P4]_Contractors Manual
P. 76
panel must display the reset code.R A F T
4.4.3 Fire Alarm
Design, supply and install a fire alarm system
in accordance with BS5839, as the project
drawings.
The design should note the requirements of
Section 1- part 6, Section 4 -part 36, 39 & 41,
Section 6 - part 44 & 45 in particular.
The system should incorporate a battery backed
control panel, manual call points, automatic
detectors and sounders, as required by Building
Inspector and Fire Officers for each specific
project.
The control panel shall incorporate a facility
to link with other fire alarm systems within the
complex, where required, so that fire signals can
D
be received from others as well as transmitting a
fire signal to others.
The panel MUST display the emergency number
to call in the event of faults to the system. The
All wiring to the fire alarm system shall be
carried out using concealed BASEC certified
red sheathed mineral insulated or fire resistant/
performance cabling complying with BS6360
Class 2 and meeting the requirements of BS6387
Category CWZ.
Allow to demonstrate the system to the
franchisee at handover.
4.4.3 Fire Alarm 3 February 2016