       4.4.3 Fire Alarm
       Design,  supply  and  install  a  fire  alarm  system
       in  accordance  with  BS5839,  as  the  project
       drawings.

       The  design  should  note  the  requirements  of
       Section  1-  part  6,  Section  4  -part  36,  39  &  41,
       Section 6 - part 44 & 45 in particular.

       The system should incorporate a battery backed
       control  panel, manual call  points, automatic
       detectors and sounders, as required by Building
       Inspector  and  Fire  Officers  for  each  specific
       project.


       The  control  panel shall incorporate  a facility
       to  link  with  other  fire  alarm  systems  within  the
       complex, where required, so that fire signals can
                            D
       be received from others as well as transmitting a
       fire signal to others.

       The panel MUST display the emergency number
       to call in the event of faults to the system. The

       All  wiring  to  the  fire  alarm  system  shall  be
       carried  out  using  concealed  BASEC  certified
       red sheathed mineral insulated or fire resistant/
       performance  cabling  complying  with  BS6360
       Class 2 and meeting the requirements of BS6387
       Category CWZ.


       Allow to demonstrate the system  to the
       franchisee at handover.