•  single reed magnetic contacts to the front A F T


          4.4.5 Security System
          A security alarm system is  mandatory for all         Main  contractor  to  supply  and  install  power
          stores.                                               supplies  for  the  security alarm as necessary,
                                                                including  a  13A  fused  spur  above  the  drivers
          The  system  shall  be  designed,  supplied  and      door for an electrically operated lock.
          installed by a NACOSS approved alarm installer.
          A  typical  installation  will  include  the  following   Access Control – The pizza delivery drivers door
          items but may vary as recommended  by the             must have access control. This will normally be
          specialist contractor and MUST always comply          a  door  secured  by  an  electro-magnetic  lock
          with  the  latest  ACPO  requirements,  including     or some other  form of electrically operated
          dual  signaling  and  dual  activation  for  police   locking  device.  As  standard,  it  should  be
          response.                                             released from the inside by a robust push button
                            D R
                                                                and from the outside by a proximity reader and
          NOTE: the comment in 4.4.4 Telephone System, regarding   programmable key fobs or similar device.
          the need for  an extra “9” to be programmed  into the
          communication system to connect to BT Featureline.    It is essential that the  lock ‘fails  safe’ and
                                                                releases  automatically  in  the  event  of  a  fire
                                                                alarm activation.
             and rear doors,
          •  passive infra red detectors to the customer        The driver’s door must have an automatic closer
             area, office and rear corridor,                    fitted  and  this  must  be  correctly  adjusted  to
          •  personal attack buttons to  the  customer          ensure proper locking without either excessive
             service counter and office                         force or time delay
          •  control panel and keypad in the office
          •  Redcare or approved alternative signalling
          •  Final Exit keypad at nominated door.