safe position (These sockets should be on A F T
4.4.7 Validator Safe 4.4.8 Door Bell
The “Validator” safe is standard - necessary a) Supply and install a push button operated
power and telecoms wiring must be installed in door bell to the back door. The unit shall be
all new stores. transformer fed from the main supply and
provide a continuous ringing tone clearly
• The site electrician should run one CAT-5E audible in both the Manager’s office and main
cable from the Validator safe, to the position shop area.
of the Modem/ADSL socket under the front
counter - to be finished at both ends with an b) Supply and install a push button operated
RJ45 socket. door bell to the shopfront door for customer
• It is then up to the safe company to provide assistance purposes.
the necessary patch cables and plug it in
D R
• The sockets for this should be labeled “SAFE”
at both ends.
• The electrician should also provide a single
13a unswitched fused spur with cable outlet
and a double 13a unswitched socket at the
one dedicated clean (red socket) circuit).
• The data/power sockets need to be either
offset slightly to one side, or above the safe,
so that staff can get to them.
Safe dimensions:
1110mm(H)x540mm(W)x520mm(D) inc. hinges.
In addition a small printer will sit on top.
4.4.7 - 4.4.8 Validator Safe and Door Bell 3 February 2016