       and adopted 5 - year water system facility development plan based on standards.
       Using the modified Dannenberg’s (1994) design which is to describe and analyze, design and
       develop based on the compliance on a certain standard..
              The following are  the Salient Findings:  1. Some part of the drainage system does not
       conform with  section 131 of the National Plumbing Code Standards, that waste water should not
       mix with storm water,  2.The number of drinking fountains does not meet the required standard
       based on ratio 1 unit is to 75 students, there are 7 existing units with more than 9,000 students,
       so the university needs to install 118 units more,  3. Toilets for Male and female students are
       not enough to cater the present population of the University.  4. Galvanized iron pipes are still
       used in old buildings,   5. Water closets, lavatories and urinals for male and female students
       are not sufficient if standards of the Plumbing Code of the Philippines are required,  6.  There
       are no urinals for male employees in offices toilets, 7. There is no water treatment facility in the
       university, 8.  Ground water level goes up to one meter during rainy season causing overflow
       to septic tanks and   9. High consumption of electricity bill up to 35 % increase due to so many
       motorized pumps used in supplying water to the university.
              Based on the conditions of the existing Urdaneta City University water system facilities,
       the  following  are  the  conclusions  drawn  from  the  findings:    1.    It  is  required  to  close  the
       discrepancies shown among the existing water system facilities and the proposed water system
       facilities, 2. Follow standards based on the Plumbing Code of the Philippines and  3 . The 5 year
       water system facility development plan of the Urdaneta City University, build up in this study  is a
       workable plan that could serve as a basis for implementation or could be modified and executed.
              The  following  are  the  recommendations  based  on  the  conclusions: 1. Frequent
       monitoring of the 5 year water system facilities of the 5 development plan is extremely suggested,
       2.  Active  participation  in  decision  making  is    strongly  recommended,  as  a  consequence  of
       agreement and synchronization, 3.  The 5 year Water System Facility Development Plan is very
       much advocated to serve as a basis for the implementation of the project at Urdaneta City
       University,  4.  The data or information on the present status of the water system facility of the
       Urdaneta City University indicates that it needs improvement and should follow standards of
       the National Plumbing Code, 5. There should be a well planned water system facility to be used
       in upgrading the  water system  efficiently and effectively and 6. The proposed water system
       facility should be constructed in accordance with the standards of the Plumbing Code of the
       Philippines.