ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility   Florida Hospital Orlando-Med Plaza      Inspector  Steve Gourley
          City/State  Orlando, FL                             Date       11-30-17        Page       1 of 2
          Contractor  n/a                                     Facility Contact   Darrell Huckaby

          Area Served   1.5T MRI                              Floor/Bldg   1  Floor Med Plaza
                                                                           st

           Zone Valve Location for this Area   Wall across from 1.5 T MRI   ZVB Manufacturer   Chemetron

         FL Hosp. Tag #          O2 #000000234086  AIR #000000234084  VAC #000000234085
          Location IAW NFPA 99   Pass               Labeled      Pass     Gauges     Fail      Leak Test   Pass
           Test Gauge   O2    52    AIR    49   VAC    -25
           Pressure vs.
           ZVB Gauge          54           54          -27

           Valve Size      1/2          1/2         3/4
          Comments: MED AIR gauge on ZVB reads high


         Gas/Pipeline Purity  Oxygen       Med Air        Comments
         Hydrocarbons               <1 PPM        <1 PPM
         Dew Point                     -46             23
         Carbon Monoxide            <1 PPM        <1 PPM
         Carbon Dioxide             <1 PPM       370 PPM
         Gas Concentration         99.9%O2     21.0 (%O2)
         Particulates                   <1             <1

         Odor/Discoloration           None          None
         Test Location             1.5T MRI      1.5T MRI

         Area Alarm Panel Location for this Area         Corridor wall next to ZVB

         Location IAW NFPA 99       Pass                 Labeled    Pass   Gauges     Pass     Leak Test   Pass
         Area Alarm Panel Manufacture Data         Amico Alert  #000000222694
                     GAUGE     LOW      HIGH                        TEST
          GAS/VAC      PSI    ALARM    ALARM    VISUAL   AUDIBLE   SWITCH   SENSOR        COMMENTS        PASS/FAIL
            OXY        52       40       60       P        P         P         PS                           PASS
             AIR       49       40       60       P        P         P         PS                           PASS
            VAC        26       12        -       P        P         P         PS                           PASS
           PS= Patient Side   SS= Source Side   NW= Not Working   CNT= Could Not Test   NA = Not Applicable    NP = Not Present