ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility   Florida Hospital Orlando-Med Plaza      Inspector  Steve Gourley
          City/State  Orlando, FL                             Date       11-30-17        Page       1 of 2
          Contractor  n/a                                     Facility Contact   Darrell Huckaby

          Area Served   3T MRI                                Floor/Bldg   1  Floor Med Plaza
                                                                           st

           Zone Valve Location for this Area   Corridor wall across from gen. waiting area.   ZVB Manufacturer   Medaes

         FL Hosp. Tag #          O2/MA/VA-P-5PN-01-B-Z-W-06
          Location IAW NFPA 99   Pass               Labeled      Pass     Gauges     Pass      Leak Test   Pass
           Test Gauge   O2    52    AIR    49   VAC    -25
           Pressure vs.
           ZVB Gauge          53           45          -26

           Valve Size      1/2          1/2         3/4
          Comments:


         Gas/Pipeline Purity  Oxygen       Med Air        Comments
         Hydrocarbons               <1 PPM        <1 PPM
         Dew Point                     -46             23
         Carbon Monoxide            <1 PPM        <1 PPM
         Carbon Dioxide             <1 PPM       370 PPM
         Gas Concentration         99.9%O2     21.0 (%O2)
         Particulates                   <1             <1

         Odor/Discoloration           None          None
         Test Location              3T MRI         3T MRI

         Area Alarm Panel Location for this Area         Corridor wall next to ZVB

         Location IAW NFPA 99       Pass                 Labeled    Pass   Gauges     Pass     Leak Test   Pass
         Area Alarm Panel Manufacture Data         Amico Alert (GP-L-5PN-01-3G-004)
                     GAUGE     LOW      HIGH                        TEST
          GAS/VAC      PSI    ALARM    ALARM    VISUAL   AUDIBLE   SWITCH   SENSOR        COMMENTS        PASS/FAIL
            OXY        53       40       60       P        P         P         PS                           PASS
             AIR       50       40       60       P        P         P         PS                           PASS
            VAC        23       12        -       P        P         P         PS                           PASS
           PS= Patient Side   SS= Source Side   NW= Not Working   CNT= Could Not Test   NA = Not Applicable    NP = Not Present


              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”