MEDICAL MANIFOLD SYSTEM ANNUAL INSPECTION FORM

          Facility            Florida Hospital Orlando Med Plaza     Technician  Anthony Voight
          City/State          Orlando, FL                            Date         12-12-17

          System Inspected    CO2 Manifold                           Floor/Bldg   Loading dock
          Manufacturer        Amico                                  Equipment ID #     GM-P-5PC-01-C2-E-06
          Model#              M2HD-DHHH-U-CO2                        Serial #           20100121-W-A

          Manifold Type       HP                                     Gas Type           CO2
          Primary Cylinders   2            Secondary Cylinders   2           Reserve Cylinders   -

                  Is Manifold System located IAW NFPA 99 (Dedicated Enclosure, Adequately Ventilated, with Required Utilities, Minimum 1-HR
           YES    Fire Rated, Electrical Devices located at or above 5 ft)
           YES    Is Manifold System Fed from Emergency Power (Essential Electrical System)
           YES    Is the Manifold Enclosure free of any Flammable Materials, Liquids or Gases
           YES    Are all Gas Cylinders (Full, Empty, Connected or unconnected) Secured to prevent them from falling
           YES    Is the Manifold Enclosure Secured and properly labeled IAW NFPA 99
                  Does the Manifold System consist of at least (2) Two Banks of Cylinders/Containers each capable of supplying an average
           YES    day’s supply of gas IAW NFPA 99
           YES    Does Each Bank/Header of Cylinders/Containers have an Isolation Valve
           YES    Does each Cylinder/Container Connection on the Header have a Check Valve to prevent backflow
           YES    Does each Bank/Header of Cylinders have a Pressure Gauge to indicate Header Contents

           YES    Does each Bank/Header have a Primary/Bank Regulator
           YES    Are there Check Valves installed between Primary/Bank Regulators and Final Line Regulators
           YES    Are Gas Cylinders/Containers prevented from exposure to Temperatures above 130 F
           YES    Does the Manifold have Duplex Final Line Regulators
           YES    Does the Manifold have the Pressure Relief Valves Required IAW NFPA 99

           YES    Are the Pressure Relief Valves Vented to the Outside IAW NFPA 99
           YES    Does the Manifold provide an Automatic Means for the Secondary Supply to Supply the System (Switchover)
           YES    Is the Manifold System Equipped with a Source Shut Off Valve & Labeled Properly
           YES    Are the Local Alarms Required by NFPA 99 Present, Functioning and connected to the Master Alarms as required
          Comments: