MEDICAL AIR SYSTEM ANNUAL INSPECTION FORM

          Facility  Florida Hospital Orlando-Med Plaza         Technician       Anthony Voight
          City/State   Orlando, FL                             Date             12-12-17

          System Inspected    Med Air System                   Floor/Bldg       Med Plaza Basement Mech.
          Manufacturer        Beacon Medaes                    Equipment ID #   CM-H-5CC-GR-0-F-0A1
          Compressor Configuration    Duplex Recip.            Motor HP         7.5HP

          Hours                      Comp #1  5206                                Comp #2  6259


                  Is Medical Air System located IAW NFPA 99 (Dedicated Mechanical Equipment Room, Adequately Ventilated, with Required
           YES    Utilities, Minimum 1-HR Fire Rated)
           YES    Is Medical Air System Fed from Emergency Power (Essential Electrical System)
                  Do the Medical Air Compressors meet the requirements of NFPA 99 (Elimination of oil anywhere in the compressor,
           YES    separation of the oil containing section by seal(s) with atmospheric vents
                  Is the Medical Air System connected ONLY to the Medical Air Distribution System and used ONLY in the application of Human
           YES    Respiration, and calibration of Medical Devices for Human Respiration

           YES    Does the Medical Air System consist of at least (2) Two Compressors
           YES    Is the Medical Air Intake & Discharge connected to the Piping by Flexible Connectors
           YES    Is the Medical Air Intake located IAW NFPA 99
           YES    Is there a Discharge Isolation Valve, Check Valve and Pressure Relief Valve for each Compressor

           YES    Is there at least Duplex After Coolers w/Condensate Drain Traps for the System
                  Is the Medical Air Receiver Corrosion Resistant & equipped with a Pressure Relief Valve, Automatic Drain, Manual Drain, Sight
           YES    Glass, Pressure Indicator and Valved Bypass Arrangement
           YES    Is the Medical Air System equipped with at least Duplex Dryers    Desiccant                 x   Refrigerant

           YES    Is the Medical Air System Equipped with at least Duplex Final Line Regulators with Pressure Indicators
           YES    Is the Medical Air System Equipped with at Least Duplex Final Line Filters with Continuous Visual Indicator
           YES    Can the Medical Air Compressors, Dryers, Filters & Regulators be Isolated for Service without shutting down the system

           YES    Is the Medical Air System Equipped with a ¼” Sample Port Valve and Source Shut Off Valve
           YES    Is the Medical Air System Equipped with a Dew Point & Co Monitor
           YES    Are the Local Alarms Required by NFPA 99 Present, Functioning and connected to the Master Alarms as required
          Comments:




              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”
                                                     www.medgaspro.org