LIST OF DISCREPANCIES 2017 Page 1 of 2
Facility Florida Hospital Orlando Med Plaza Inspector Anthony Voight
City/State Orlando, FL Facility Contact Darrell Huckaby
Contractor n/a Floor/Bldg All
Area Served Bed/Room # Discrepancy Disc Repair Status
Master Alarms
1 Area Maint. Shop Basement Loc. #2 N2 Bank #1 In Reserve, No Visual
2 Area Maint. Shop Basement Loc. #2 N2 Bank #2 In Reserve, No Visual
3 Area Maint. Shop Basement Loc. #2 CO2 Reserve In Use, No Visual
1 Floor
st
4 1.5T MRI ZVB Gauges fail, Med Air reading high.
5 Decontamination ZVB No ZVB for N2 in Decontamination Room
6 Decontamination Decon. Rm. Air needs to be blanked off
Outlets have no pressure, they need to be
7 Gamma Knife blanked off if not in use.
Found light discoloration in N2O during
8 LITHO 3 LITHO 3 Purity Test.
Found heavy discoloration in N2O during
9 OR 1 OR 1 Purity Test
10 OR 4 OR 4 VAC outlet #3, Adapter Does Not Latch
Labeling fails, tags on piping in ZVB should
11 PACU Beds 1-5 ZVB read PACU Beds 1-5
Labeling fails, tags on pipe in ZVB should
12 PEDS 1-8 ZVB read Patient Rooms 1-8
PEDS 9-12 Labeling fails, tags inside ZVB should read
13 & PACU 1-2 ZVB PEDS 9-12 & PACU 1-2
Found light particulates/discoloration in O2
14 Recovery Beds 6-9 Bed 7 and Air during Purity Test
15 Recovery Beds 6-9 Alarm Labeling fails.
16 Recovery Beds 6-9 Alarm Normal light is out for Oxy
Found light particulates/discoloration in Air
17 Sedation 1 Sedation 1 during Purity Test
Treatment Units 1 thru 4,
Oncology Patient Hold, Exam Labeling fails, should read Treatment Units
Rooms 1 thru 6, 8 & 9 Virtual 1 thru 4, Oncology Patient Hold, Exam
Simulation, Meg Suite, & Soiled Rooms 1 thru 6, 8 & 9 Virtual Simulation,
18 Utility ZVB/Alarm Meg Suite, & Soiled Utility
19 X-ray X-ray VAC outlet #1, Adapter Does Not Latch