Page 211 - Med Plaza and Cancer Center
P. 211

"Oil-Less” Medical Air                                                              Medical Systems



               Appendix A - Desiccant Dryer

               A.4.1 Maintenance Schedule

                                    20 hp Triplex, 15 hp Quad (Type 2 Dryer) 155 cfm
                          Service Interval     Part number            Description         Quantity
                             Every year        ELM 22 005              Pre-filter             2
                             Every year        ELM 22 005             After-filter            2
                             Every year        MUF 01 008            Purge muffler            2
                            Every 5 years       DES 01 001             Desiccant           9 bags
                            Every 5 years       VAL 01 013            Check valve             4
                            Every 5 years       GKT 10 008           Tower o-ring             4
                            Every 5 years       GKT 10 007           Canister o-ring          4
                             As needed         VAL 11 003           Switching valve           2
                             As needed         GAG 01 032         Tower pressure gauge        2
                                          Purge valve (Refer to diagram for correct valve)
                            Every 5 years       VAL 04 020            Diaphragm               2
                            Every 5 years       VAL 04 031              Poppet                2

                                            20 hp Quad (Type 2 Dryer) 200 cfm
                          Service Interval     Part number            Description         Quantity
                             Every year        ELM 22 006              Pre-filter             2
                             Every year        ELM 22 006             After-filter            2
                             Every year        MUF 01 008            Purge muffler            2
                            Every 5 years       DES 01 001             Desiccant           11 bags
                            Every 5 years       VAL 01 013            Check valve             4
                            Every 5 years       GKT 10 008           Tower o-ring             4
                            Every 5 years       GKT 10 007           Canister o-ring          4
                             As needed         VAL 11 003           Switching valve           2
                             As needed         GAG 01 032         Tower pressure gauge        2
                                          Purge valve (Refer to diagram for correct valve)
                            Every 5 years       VAL 04 020            Diaphragm               2
                            Every 5 years       VAL 04 031              Poppet                2




























                                                            A-12
   206   207   208   209   210   211   212   213   214   215   216