Specifications
Chapter 1: Introduction
Specifications
For MedPlus TotalAlert ™ Alarm Network specifications, refer to table 1-10
on page 1-40 through table 1-15 on page 1-41.
Refer to table 1-16 on page 1-42 for the types of existing alarms that can be
converted to a MedPlus TotalAlert™ Alarm Network—Master Alarm,
MedPlus TotalAlert™ Alarm Network—Area Alarm, or MedPlus TotalAlert™
Alarm Network—Combination Alarm. Also included in the table are the sizes
that the existing rough-in boxes need to be, and the conversion kits that replace
those existing alarms.
Table 1-10. Power Specifications
Facility Power Specifications Ratings
Supply voltage for single power supply alarms 120 V AC, 60 Hz
Breaker for single power supply alarms 15 A
Supply voltage for dual power supply alarms 120 V AC, 60 Hz
Breaker for dual power supply alarms 15 A
Field power supply wiring 12 gauge
Fuse rating for internal power supply (except for the 0.5 Amp Slo-Blo® a
Master Alarm plus Six Area Alarm Modules)
Fuse rating for internal power supply on the Master 0.75 Amp Slo-Blo®
Alarm plus Six Area Alarm Modules
a. Slo-Blo® is a registered trademark of Littelfuse, Inc.
Table 1-11. Cabling Requirements from the Area Alarm Module to the
Transducer
Specifications Dimensions
Distance Maximum 4500' (1372 m)
Cable Stranded, 22-gauge, shielded, twisted-
pair, three-conductor cable
Signal Power 15 V DC, 75 mA maximum
Page 1 - 40 MedPlus TotalAlert™ Alarm Network Operation and Maintenance Manual (man291ra)