Page 791 - Med Plaza and Cancer Center
P. 791

PROPRIETARY AND CONFIDENTIAL DRAFT 28/Feb/03

                   Medical Gas Alarm Network System Interaction
                   Chapter 3: Theory of Operation

                          Master Alarm Wiring Conventions

                                 The following section provides an overview of typical wiring conventions for
                                 Master Alarm inputs and outputs (see figure 3-2 on page 3-9):

                                   • To have the most reliable switch signalling, Hill-Rom recommends using
                                     input switches and relays having contacts that match the following Master
                                     Alarm electrical characteristics:

                                      •   Low voltage (approximately 20V AC)
                                      •   Low current (approximately 10 mA)

                                      •   Dry circuit applications

                                 NOTE:
                                 Refer to the wiring instructions from the manufacturer for specific switches
                                 and relays.

                                   • To comply with the NFPA 99 standard, every switch and relay must have
                                     separate wiring to each Master Alarm.
                                   • Polarity is determined by the indicators on the Master Alarm Breakout P.C.
                                     Boards. Switches and contacts on signalling devices are not usually marked
                                     with polarity indicators.
                                   • When Master Alarms share input signals from the same pair of contacts on
                                     switches or relays, polarity between each Master Alarm must be
                                     maintained.
                                   • Low pressure sensing switches are typically wired from the normally open
                                     and common contacts to each Master Alarm.

                                      •   Maintain polarity by wiring the normally open contact wire to the
                                          positive (+) terminal and the common contact wire to the negative (-)
                                          terminal.

                                 NOTE:
                                 Normally open and normally closed refer to the state of the switch or relay in
                                 its “shelf position” (the position of the switch or relay before the system is
                                 operational).
                                   • High pressure sensing switches are typically wired from the normally
                                     closed and common contacts to each Master Alarm.
                                      •   Maintain polarity by wiring the normally closed contact wire to the
                                          positive (+) terminal and the common contact wire to the negative (-)
                                          terminal.
                                   • Switches sensing both high pressure and low pressure have independently
                                     operating sets of contacts, one set for low pressure and one for high
                                     pressure.



                   Page 3 - 8            MedPlus TotalAlert™ Alarm Network Operation and Maintenance Manual (man291ra)
   786   787   788   789   790   791   792   793   794   795   796