Page 210 - Womens Pavilion
P. 210
“Oil-Less” Scroll Medical Air
6.0 Inspection/Replacement Procedures
6.7 General Inspections
6.7.1 Monthly Inspection
A general inspection should be performed on a
regular basis (monthly) for safety items. Items to
inspect include all wiring, fl ex hoses, and other
items. If a damaged item is viewed, call your local
BeaconMedaes service technician for a thorough
inspection and report of fi ndings.
6.7.2 Every Six Months
A thorough inspection of the compressor cooling-
air discharge grating and the aftercooler coils
should be performed at least every six months or
more frequently if conditions require. If a dust/
dirt buildup is visible, clean the grating or coils
to remove the buildup. Excess dust/dirt buildup
in these areas will prevent air from cooling the
compressor unit or the aftercooler, aff ecting
performance of the air system.
6-7 4107 9000 69.06