Page 218 - Womens Pavilion
P. 218
“Oil-Less” Scroll Medical Air
Appendix A: Desiccant Dryer
A.1 General Information Manual Mode
When the dryer is in the “Manual” mode, the
CAUTION: This manual is designed to serve as dryer will shift towers every 30 seconds. At normal
the operation and maintenance guide for your operating conditions, one tower is at system
dryer, if equipped. The contents of this manual pressure and the other tower is at 0 p.s.i. Any
should be carefully read BEFORE attempting any condition other than this is not normal and will
phase of operation or maintenance. Failure to cause a high dew point condition. During tower
follow the operating and maintenance procedures changeover, the online chamber will exhaust,
of the instruction manual could result in personal and the chamber that is regenerating (purging)
injury or property damage. will come to line pressure. There is a fi ve second
re-pressurization cycle. If the dryer is in the
All information, specifi cations and illustrations continuous purge cycle (Manual Mode), the dryer
within this manual are those in eff ect at the time will use 15% of the NFPA system capacity to purge
of printing. The manufacturer reserves the right to the dryer.
change or make improvements without notice and
without incurring any obligation to make changes Automatic Mode
or add improvements to products previously sold. When the dryer is in the “Automatic” mode, the
dew point monitor controls the dryer purge, and
When requesting information, service, ordering of purging depends on the dew point condition.
spare parts, etc., please reference all information When the dew point reading is above the setpoint
supplied on the serial number plate located on of -10ºC (14ºF), the dryer will function normally
the side of the control panel. (one tower at system pressure, one tower at 0
p.s.i.). When the dew point is below the setpoint
To facilitate maintenance, recommended spare of -10ºC (14ºF), the purge valve will close. In this
parts for your specifi c dryer model are available. condition both towers will be approximately 100
Failure to maintain recommended spare parts p.s.i. and the dryer will not shift towers until the
and fi lter cartridges might result in expensive and dew point is above -10ºC (14ºF).
unnecessary downtime for which the manufacturer
cannot be responsible. To request a quotation of, A.1.2 Pre-fi lter
or place an order for, recommended or emergency
spare parts, please contact BeaconMedæs Service As the fi rst line of defense against water
at 1-888-4MEDGAS. contaminants, a coalescing pre-fi lter with an
automatic drain is installed. The coalescing pre-
A.1.1 Drying Cycles fi lter removes water aerosols from the gas stream
before the gas enters the dryer. Liquids collected
This fully automatic, heatless type dryer alternately by the assembly’s fi lter cartridge(s) fall to the
cycles the compressed, process gas fl ow through housing sump and are drained by a fl oat drain.
two desiccant charged towers where the entrained, Installer should pipe these drain connections to a
vaporous moisture content of the gas is adsorbed. common drain point.
One desiccant tower is always on-line in a drying
cycle throughout normal dryer operation. The
opposite, off -line tower is in a regeneration cycle
for removal of the previously adsorbed moisture
content or in a purge saving cycle at line pressure.
A-1 4107 9000 69.06