“Oil-Less” Scroll Medical Air


            Appendix A: Desiccant Dryer



            A.3 Troubleshooting

             Problem                    Possible Causes                    Solution

             Dew point degradation      Desiccant is contaminated.  The    Shutdown and depressurize the dryer.
                                        “white” desiccant beads may        Inspect the desiccant and replace if
                                        appear discolored and dirty if     fouled.  Inspect any existing pre-fi lter
                                        contamination has occurred.        if fouling is noted.

                                        Union or other piping/             Soap test the dryer outlet manifold
                                        component leaks at dryer outlet    and piping downstream of dryer.
                                        manifold or downstream of dryer  Repair all leaks noted.
                                        outlet.

             Back pressure on a         Dirty or fouled purge muffl  er    Switch off  power and remove purge
             desiccant chamber during                                      muffl  er and clean using an air nozzle,
             the regeneration cycle.                                       or replace.

                                        Outlet check valve leaking         Repair check valve


            NOTE:   The presence of backpressure will result in insuffi  cient regeneration followed by dew point
            degradation.  An off -line chamber’s pressure MUST be less than 3 psig throughout all regeneration
            cycles.