        SIGNAL INPUT SELECTION                                                                        Version
                                                                                                3                  4


        Factory Default - Normally Closed as per NFPA 99.

        The Amico alarm can detect eld devices in the Normally Open or Normally Closed position.

        For Normally Closed   Set switch #3 to the OFF position.

        For Normally Open     Set switch #3 to the ON position.





        PLEASE NOTE: The above signal input selection, applies to both alarm systems - the Master/NEMA 4
        and the 2 in 1.


        MAINTENANCE  MODE


               Factory Default - Disabled

        The Maintenance (or Latch) mode is used to allow hospital personnel to identify loose wiring or faulty source equipment.
        By putting the master module into “Latch” mode, any alarms received; even transient ones, will be latched-on so that
        maintenance personnel can identify the source of the problem. The Maintenance mode will disable the automatic reset,
        if a fault condition has been rectied. The alarm indicator can only be turned-o by pushing the “alarm silence” button
        on the annunciator module twice. The “Maintenance” LED will illuminate whenever the maintenance mode is enabled.








        Disable        Set switch #4 to the OFF position.




        Enable         Set switch #4 to the ON position.