P. 192
MEANS OF EGRESS
[BE] 1009.4 Elevators. In order to be considered part of an [BE] 1009.6.4 Separation. Each area of refuge shall be
accessible means of egress, an elevator shall comply with separated from the remainder of the story by a smoke bar-
Sections 1009.4.1 and 1009.4.2. rier complying with Section 709 of the International
[BE] 1009.4.1 Standby power. The elevator shall meet Building Code or a horizontal exit complying with Section
the emergency operation and signaling device require- 1026. Each area of refuge shall be designed to minimize
ments of Section 2.27 of ASME A17.1/CSA B44. Standby the intrusion of smoke.
power shall be provided in accordance with Chapter 27 Exceptions:
and Section 3003 of the International Building Code.
1. Areas of refuge located within an enclosure for
[BE] 1009.4.2 Area of refuge. The elevator shall be interior exit stairways complying with Section
accessed from an area of refuge complying with Section 1023.
1009.6.
2. Areas of refuge in outdoor facilities where exit
Exceptions:
access is essentially open to the outside.
1. Areas of refuge are not required at the elevator in
open parking garages. [BE] 1009.6.5 Two-way communication. Areas of refuge
shall be provided with a two-way communication system
2. Areas of refuge are not required in buildings and complying with Sections 1009.8.1 and 1009.8.2.
facilities equipped throughout with an automatic
sprinkler system installed in accordance with [BE] 1009.7 Exterior areas for assisted rescue. Exterior
Section 903.3.1.1 or 903.3.1.2. areas for assisted rescue shall be accessed by an accessible
route from the area served.
3. Areas of refuge are not required at elevators not
required to be located in a shaft in accordance Where the exit discharge does not include an accessible
with Section 712 of the International Building route from an exit located on the level of exit discharge to a
Code. public way, an exterior area of assisted rescue shall be pro-
4. Areas of refuge are not required at elevators serv- vided on the exterior landing in accordance with Sections
ing smoke protected or open-air assembly seating 1009.7.1 through 1009.7.4.
areas complying with Sections 1029.6.2 and [BE] 1009.7.1 Size. Each exterior area for assisted rescue
1029.6.3. shall be sized to accommodate wheelchair spaces in accor-
5. Areas of refuge are not required for elevators dance with Section 1009.6.3.
accessed from a refuge area in conjunction with a [BE] 1009.7.2 Separation. Exterior walls separating the
horizontal exit. exterior area of assisted rescue from the interior of the
[BE] 1009.5 Platform lifts. Platform lifts shall be permitted building shall have a minimum fire-resistance rating of 1
to serve as part of an accessible means of egress where hour, rated for exposure to fire from the inside. The fire-
allowed as part of a required accessible route in Section resistance-rated exterior wall construction shall extend
1109.8 of the International Building Code except for Item 10. horizontally not less than 10 feet (3048 mm) beyond the
Standby power for the platform lift shall be provided in landing on either side of the landing or equivalent fire-
accordance with Chapter 27 of the International Building resistance-rated construction is permitted to extend out
Code. perpendicular to the exterior wall not less than 4 feet
[BE] 1009.6 Areas of refuge. Every required area of refuge (1220 mm) on the side of the landing. The fire-resistance-
shall be accessible from the space it serves by an accessible rated construction shall extend vertically from the ground
means of egress. to a point not less than 10 feet (3048 mm) above the floor
level of the area for assisted rescue or to the roof line,
[BE] 1009.6.1 Travel distance. The maximum travel dis-
tance from any accessible space to an area of refuge shall whichever is lower. Openings within such fire-resistance-
not exceed the exit access travel distance permitted for the rated exterior walls shall be protected in accordance with
occupancy in accordance with Section 1017.1. Section 716 of the International Building Code.
[BE] 1009.6.2 Stairway or elevator access. Every Exception: The fire-resistance rating and opening pro-
required area of refuge shall have direct access to a stair- tectives are not required in the exterior wall where the
way complying with Sections 1009.3 and 1023 or an ele- building is equipped throughout with an automatic
vator complying with Section 1009.4. sprinkler system installed in accordance with Section
903.3.1.1 or 903.3.1.2.
[BE] 1009.6.3 Size. Each area of refuge shall be sized to
accommodate one wheelchair space of 30 inches by 48 [BE] 1009.7.3 Openness. The exterior area for assisted
inches (762 mm by 1219 mm) for each 200 occupants or rescue shall be open to the outside air. The sides other than
portion thereof, based on the occupant load of the area of the separation walls shall be not less than 50 percent open,
refuge and areas served by the area of refuge. Such wheel- and the open area shall be distributed so as to minimize the
chair spaces shall not reduce the means of egress mini- accumulation of smoke or toxic gases.
mum width or required capacity. Access to any of the [BE] 1009.7.4 Stairways. Stairways that are part of the
required wheelchair spaces in an area of refuge shall not means of egress for the exterior area for assisted rescue
be obstructed by more than one adjoining wheelchair
space.
2018 INTERNATIONAL FIRE CODE ® 159