MEANS OF EGRESS



             [BE] 1009.4 Elevators. In order to be considered part of an  [BE] 1009.6.4 Separation. Each area of refuge shall be
             accessible  means of  egress, an elevator  shall comply with  separated from the remainder of the story by a smoke bar-
             Sections 1009.4.1 and 1009.4.2.                         rier complying with Section 709 of the  International
               [BE] 1009.4.1 Standby power. The elevator shall meet  Building Code or a horizontal exit complying with Section
               the emergency operation  and signaling device require-  1026. Each area of refuge shall be designed to minimize
               ments of Section 2.27 of ASME A17.1/CSA B44. Standby  the intrusion of smoke.
               power shall  be provided in  accordance  with Chapter 27  Exceptions:
               and Section 3003 of the International Building Code.
                                                                         1. Areas of refuge located within an enclosure for
               [BE] 1009.4.2 Area  of refuge. The elevator shall be         interior exit stairways  complying with  Section
               accessed from an area of refuge complying with Section       1023.
               1009.6.
                                                                         2. Areas of refuge in  outdoor facilities where  exit
                  Exceptions:
                                                                            access is essentially open to the outside.
                    1. Areas of refuge are not required at the elevator in
                       open parking garages.                         [BE] 1009.6.5 Two-way communication. Areas of refuge
                                                                     shall be provided with a two-way communication system
                    2. Areas of refuge are not required in buildings and  complying with Sections 1009.8.1 and 1009.8.2.
                       facilities equipped throughout with an automatic
                       sprinkler system installed in accordance with  [BE] 1009.7 Exterior  areas for assisted  rescue. Exterior
                       Section 903.3.1.1 or 903.3.1.2.            areas for assisted rescue shall be accessed by an accessible
                                                                  route from the area served.
                    3. Areas of refuge are not required at elevators not
                       required to  be located  in  a shaft in accordance  Where the  exit discharge does not include an  accessible
                       with Section 712 of the  International Building  route from an exit located on the level of exit discharge to a
                       Code.                                      public way, an exterior area of assisted rescue shall be pro-
                    4. Areas of refuge are not required at elevators serv-  vided on the  exterior landing in accordance  with  Sections
                       ing smoke protected or open-air assembly seating  1009.7.1 through 1009.7.4.
                       areas complying with  Sections 1029.6.2 and   [BE] 1009.7.1 Size. Each exterior area for assisted rescue
                       1029.6.3.                                     shall be sized to accommodate wheelchair spaces in accor-
                    5. Areas of refuge are not required for elevators  dance with Section 1009.6.3.
                       accessed from a refuge area in conjunction with a  [BE] 1009.7.2 Separation. Exterior walls separating the
                       horizontal exit.                              exterior area of assisted rescue from the  interior  of the
             [BE] 1009.5 Platform lifts. Platform lifts shall be permitted  building shall have a minimum fire-resistance rating of 1
             to serve  as  part of an  accessible  means of  egress where  hour, rated for exposure to fire from the inside. The fire-
             allowed as part of a required  accessible route in  Section  resistance-rated  exterior wall construction shall  extend
             1109.8 of the International Building Code except for Item 10.  horizontally not less than 10 feet (3048 mm) beyond the
             Standby power for  the  platform  lift shall  be provided in  landing on either  side of  the landing  or  equivalent fire-
             accordance  with Chapter 27  of the  International Building  resistance-rated construction is permitted  to  extend out
             Code.                                                   perpendicular to the  exterior wall not less than 4  feet
             [BE] 1009.6 Areas of refuge. Every required area of refuge  (1220 mm) on the side of the landing. The fire-resistance-
             shall be accessible from the space it serves by an accessible  rated construction shall extend vertically from the ground
             means of egress.                                        to a point not less than 10 feet (3048 mm) above the floor
                                                                     level  of the area for assisted rescue or to the roof  line,
               [BE] 1009.6.1 Travel distance. The maximum travel dis-
               tance from any accessible space to an area of refuge shall  whichever is lower. Openings within such fire-resistance-
               not exceed the exit access travel distance permitted for the  rated exterior walls shall be protected in accordance with
               occupancy in accordance with Section 1017.1.          Section 716 of the International Building Code.
               [BE] 1009.6.2 Stairway or  elevator access. Every       Exception: The fire-resistance rating and opening pro-
               required area of refuge shall have direct access to a stair-  tectives are not required in the exterior wall where the
               way complying with Sections 1009.3 and 1023 or an ele-  building is equipped throughout with  an  automatic
               vator complying with Section 1009.4.                    sprinkler system installed in accordance with Section
                                                                       903.3.1.1 or 903.3.1.2.
               [BE] 1009.6.3 Size. Each area of refuge shall be sized to
               accommodate one  wheelchair space of 30 inches by 48  [BE] 1009.7.3  Openness. The exterior area for assisted
               inches (762 mm by 1219 mm) for each 200 occupants or  rescue shall be open to the outside air. The sides other than
               portion thereof, based on the occupant load of the area of  the separation walls shall be not less than 50 percent open,
               refuge and areas served by the area of refuge. Such wheel-  and the open area shall be distributed so as to minimize the
               chair spaces shall not reduce the  means of egress mini-  accumulation of smoke or toxic gases.
               mum width or required capacity. Access to any of the  [BE] 1009.7.4 Stairways. Stairways that are part of the
               required wheelchair spaces in an area of refuge shall not  means of egress for the exterior area for assisted rescue
               be  obstructed by more  than one adjoining  wheelchair
               space.