Page 196 - 2018_IFC
P. 196

MEANS OF EGRESS



                  safeguard means of egress. The forces required to open  6. The door assembly shall have an integrated
                  these doors manually shall not exceed those specified     standby power supply.
                  in Section 1010.1.3, except that the force to set the door  7. The door assembly power supply shall be electri-
                  in motion shall not exceed 50 pounds  (220 N). The        cally supervised.
                  door shall be capable of opening from any position to  8. The door shall open to the minimum required
                  the full width  of the  opening in which such  door  is
                  installed when a force is applied to the door on the side  width within  10 seconds after activation of the
                                                                            operating device.
                  from which egress is made. Power-operated swinging
                  doors, power-operated  sliding doors  and power-oper-  [BE] 1010.1.4.4  Locking  arrangements in educa-
                  ated folding doors shall comply with BHMA A156.10.   tional occupancies. In Group E and Group B educa-
                  Power-assisted swinging doors and low energy power-  tional occupancies, egress doors from classrooms,
                  operated swinging doors shall comply with BHMA       offices and other occupied rooms shall be permitted to
                  A156.19.  Low-energy power-operated sliding  doors   be provided  with locking arrangements designed to
                  and low-energy power-operated folding doors shall    keep intruders from entering the room, where all of the
                  comply with BHMA A156.38.                            following conditions are met:
                    Exceptions:                                          1. The door shall be capable of being unlocked from
                                                                            outside the room  with a  key or other  approved
                       1. Occupancies in Group I-3.
                                                                            means.
                       2. Special-purpose horizontal sliding, accordion  2. The door shall be openable from within the room
                         or folding doors complying with Section            in accordance with Section 1010.1.9.
                         1010.1.4.3.
                                                                         3. Modifications shall not be made  to listed panic
                       3. For a biparting door in the emergency break-      hardware, fire door hardware or door closers.
                         out mode, a door leaf located within a multi-
                         ple-leaf opening shall  be exempt from the      [BE] 1010.1.4.4.1 Remote operation of locks.
                         minimum 32-inch (813  mm) single-leaf           Remote operation of locks complying with Section
                         requirement of Section 1010.1.1, provided that  1010.1.4.4. shall be permitted.
                         a minimum 32-inch (813 mm) clear opening is   [BE] 1010.1.4.5  Security grilles. In Groups B, F, M
                         provided when the two biparting leaves meet-  and S, horizontal sliding or vertical security grilles are
                         ing in the center are broken out.             permitted at the main exit and shall be openable from
                  [BE]  1010.1.4.3 Special-purpose horizontal sliding,  the inside without the use of a key or special knowledge
                  accordion or folding doors. In other  than  Group H  or effort during periods that the space is occupied. The
                  occupancies, special-purpose horizontal sliding, accor-  grilles shall remain secured in the full-open position
                  dion, or folding door assemblies permitted to be a com-  during the period of occupancy by the general public.
                  ponent of  a  means of egress in accordance  with    Where two or more means of egress are required, not
                  Exception 6 to Section 1010.1.2 shall comply with all  more than one-half of the exits or exit access doorways
                  of the following criteria:                           shall be equipped with  horizontal sliding  or  vertical
                                                                       security grilles.
                    1. The doors shall be power operated and shall be
                       capable of being operated manually in the event  [BE] 1010.1.5 Floor elevation. There shall be a floor or
                       of power failure.                             landing on each side of a door. Such floor or landing shall
                                                                     be at the same elevation on each side of the door. Landings
                    2. The doors shall be openable by a simple method
                       from both sides without special knowledge or  shall be level except for exterior landings, which are per-
                                                                     mitted to have a slope not to exceed 0.25 unit vertical in 12
                       effort.
                                                                     units horizontal (2-percent slope).
                    3. The force required to operate the door shall not
                       exceed 30 pounds (133 N) to set the door in     Exceptions:
                       motion and 15 pounds (67 N) to close the door or  1. Doors serving individual  dwelling units in
                       open it to the minimum required width.               Groups R-2 and R-3 where the following apply:
                    4. The door shall be openable with a force not to         1.1. A door is permitted to open at the top step
                       exceed 15 pounds (67 N) when a force  of 250               of an  interior  flight of  stairs, provided
                       pounds (1100 N) is applied perpendicular to the            that the door does not swing over the top
                       door adjacent to the operating device.                     step.
                    5. The door assembly shall comply with the applica-       1.2. Screen doors and storm doors are permit-
                       ble fire protection rating and, where rated, shall         ted to swing over stairs or landings.
                       be  self-closing or automatic closing by smoke    2. Exterior doors as provided for in Section 1003.5,
                       detection in accordance with Section 716.2.6.6 of    Exception 1, and Section 1022.2, which are not
                       the  International Building  Code, shall be          on an accessible route.
                       installed in accordance with NFPA 80 and shall
                                                                         3. In Group R-3 occupancies not required to be
                       comply with  Section 716 of  the  International
                                                                            Accessible units, Type A units or Type B units,
                       Building Code.
                                                                            the  landing at an exterior  doorway shall be not
             2018 INTERNATIONAL FIRE CODE ®                                                                      163
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   191   192   193   194   195   196   197   198   199   200   201