MEANS OF EGRESS



                6. All clinical staff  shall  have the keys, codes or     delay  electronics have been  deactivated,
                   other means necessary to operate the locking sys-      rearming the delay  electronics shall be by
                   tems.                                                  manual means only.
                7. Emergency lighting shall be provided at the door.         Exception: Where approved, a delay of not
                8. The door locking system units shall be listed in          more than 30 seconds is permitted on a
                   accordance with UL 294.                                   delayed egress door.
                Exceptions:                                             5. The egress path from any point shall not pass
                                                                          through more than one delayed egress locking
                   1. Items 1 through 4 shall not apply to doors to       system.
                     areas occupied  by persons who, because of
                     clinical needs, require restraint or containment        Exceptions:
                     as part of the function of a psychiatric treat-           1. In Group I-2 or I-3 occupancies, the
                     ment area.                                                  egress  path from  any point in the
                   2. Items 1 through 4 shall not apply to doors to              building shall pass through not more
                     areas where a  listed egress  control system is             than  two delayed egress locking
                     utilized to reduce the risk of child abduction              systems provided that the combined
                     from nursery and obstetric areas of a Group I-2             delay does not exceed 30 seconds.
                     hospital.                                                 2. In Group I-1 or I-4 occupancies, the
              [BE] 1010.1.9.8 Delayed egress. Delayed egress lock-               egress  path from  any point in the
              ing systems, shall be permitted to be installed on doors           building shall pass through not more
              serving the following occupancies in buildings that are            than  two delayed egress locking
              equipped throughout with an automatic sprinkler sys-               systems provided that the combined
              tem  in accordance with Section 903.3.1.1 or an                    delay does  not exceed 30  seconds
              approved automatic smoke or  heat detection system                 and the building is equipped
              installed in accordance with Section 907:                          throughout  with  an   automatic
                                                                                 sprinkler system in accordance with
                1. Group B, F, I, M, R, S and U occupancies.
                                                                                 Section 903.3.1.1.
                2. Group E classrooms with an occupant load of less     6. A sign shall be provided on the door and shall
                   than 50.
                                                                          be located  above and within  12  inches (305
                Exception: Delayed egress locking systems shall be        mm) of the door exit hardware:
                permitted to be installed on exit or exit access doors,      6.1. For doors that swing in the direction of
                other than the main exit or exit access door, serving           egress, the  sign  shall read: PUSH
                a courtroom in buildings equipped throughout with               UNTIL ALARM SOUNDS. DOOR
                an  automatic sprinkler system in accordance with               CAN BE OPENED IN  15 [30]
                Section 903.3.1.1.
                                                                                SECONDS.
                [BE] 1010.1.9.8.1 Delayed egress locking system.             6.2. For doors  that swing in  the opposite
                The delayed egress locking system shall be installed            direction of egress, the sign shall read:
                and operated in accordance with all of the following:
                                                                                PULL  UNTIL ALARM SOUNDS.
                   1. The delay electronics of the delayed egress               DOOR CAN BE OPENED IN 15 [30]
                     locking system shall deactivate upon actuation             SECONDS.
                     of the automatic sprinkler system or automatic          6.3 The sign shall comply with the visual
                     fire detection  system, allowing immediate,                character requirements in ICC A117.1.
                     free egress.
                                                                             Exception: Where  approved, in Group  I
                   2. The delay electronics of the delayed egress            occupancies, the installation of a sign is not
                     locking system shall deactivate  upon loss of           required where care  recipients  who,
                     power controlling the lock or lock mechanism,           because of clinical needs, require restraint
                     allowing immediate free egress.
                                                                             or containment as part of the function of the
                   3. The delayed egress locking system shall have           treatment area.
                     the capability of being deactivated at the fire    7. Emergency lighting shall be provided on the
                     command center and other approved locations.
                                                                          egress side of the door.
                   4. An attempt to egress shall initiate an irrevers-  8. The delayed egress locking system units shall
                     ible process that shall allow such egress in not     be listed in accordance with UL 294.
                     more than 15 seconds when a physical effort
                     to exit is applied to the egress side door hard-  [BE] 1010.1.9.9 Sensor release of electrically locked
                     ware for not more than 3 seconds. Initiation of  egress doors. Sensor release of electric  locking sys-
                     the irreversible process shall activate an audi-  tems shall be permitted on doors located in a the means
                     ble signal in the vicinity of the door. Once the  of egress in any  occupancy except Group H  where