MEANS OF EGRESS



                  installed and operated in accordance with all of the fol-  [BE] 1010.1.9.11 Locking arrangements in buildings
                  lowing criteria:                                     within correctional facilities. In buildings within cor-
                    1. The sensor shall be installed on the egress side,  rectional and detention facilities, doors in  means of
                       arranged to detect an occupant approaching the  egress serving rooms or spaces occupied by persons
                       doors and shall cause the electric locking system  whose movements are controlled for security reasons
                       to unlock.                                      shall be permitted to be locked where equipped with
                                                                       egress control devices that shall unlock manually and
                    2. The electric locks shall be arranged to unlock by  by not less than one of the following means:
                       a signal from or loss of power to the sensor.
                                                                         1. Activation of an  automatic sprinkler system
                    3. Loss of power to the lock or locking system shall    installed in accordance with Section 903.3.1.1.
                       automatically unlock the electric locks.
                                                                         2. Activation of an approved manual fire alarm box.
                    4. The doors shall be arranged to unlock from a
                       manual unlocking device located 40 inches to 48   3. A signal from a constantly attended location.
                       inches (1016 mm to 1219 mm) vertically above    [BE] 1010.1.9.12 Stairway  doors. Interior  stairway
                       the floor and within 5 feet  (1524 mm) of  the  means of egress doors shall be openable from both
                       secured doors. Ready access shall be provided to  sides without the use of a key or special knowledge or
                       the manual unlocking device and the device shall  effort.
                       be clearly identified by a sign that reads “PUSH  Exceptions:
                       TO EXIT.” When operated, the manual unlock-
                       ing device shall result in direct interruption of    1. Stairway discharge doors  shall  be openable
                                                                              from the egress side and shall only be locked
                       power to the electric lock—independent of other        from the opposite side.
                       electronics—and the  electric lock  shall remain
                       unlocked for not less than 30 seconds.               2. This section shall not apply to doors arranged
                                                                              in accordance with Section 403.5.3 of the
                    5. Activation of the  building fire alarm  system,
                       where provided, shall automatically unlock the         International Building Code.
                       electric lock, and  the electric  lock shall remain  3. Stairway exit doors are permitted to be locked
                       unlocked until  the fire alarm  system has  been       from the side opposite  the egress  side, pro-
                       reset.                                                 vided that they are openable from the egress
                                                                              side and capable of being unlocked simultane-
                    6. Activation  of the building  automatic sprinkler
                       system or fire detection system, where provided,       ously without  unlatching upon a signal from
                       shall automatically unlock the electric lock. The      the fire command center, if present, or a signal
                       electric lock shall remain unlocked until the fire     by emergency personnel  from a  single loca-
                       alarm system has been reset.                           tion inside the main entrance to the building.
                                                                            4. Stairway exit doors shall be openable from the
                    7. The door locking system units shall be listed in
                       accordance with UL 294.                                egress side and shall only be locked from the
                                                                              opposite side in Group B, F, M and S occu-
                  [BE] 1010.1.9.10 Door hardware release of electri-          pancies where the only interior access to the
                  cally locked egress doors. Door hardware  release of        tenant space is from a single  exit stairway
                  electric locking systems shall be permitted on doors in     where permitted in Section 1006.3.3.
                  the means of egress in any occupancy except Group H
                  where installed and operated in accordance with all of    5. Stairway exit doors shall be openable from the
                  the following:                                              egress side and shall only be locked from the
                                                                              opposite side in Group R-2 occupancies where
                    1. The door hardware that is affixed to the door leaf     the only interior access to the dwelling unit is
                       has an obvious method of operation that is readily     from a single exit stairway where permitted in
                       operated under all lighting conditions.
                                                                              Section 1006.3.3.
                    2. The door hardware is capable of being operated  [BE] 1010.1.10 Panic and fire exit hardware. Swinging
                       with one hand and shall comply with Section   doors serving a Group H occupancy and swinging doors
                       1010.1.9.6.
                                                                     serving rooms or spaces with an occupant load of 50 or
                    3. Operation of the door hardware directly inter-  more in a Group A or E occupancy shall not be provided
                       rupts the power to the electric lock and unlocks  with a latch or lock other than panic hardware or fire exit
                       the door immediately.                         hardware.
                    4. Loss of power to the electric locking system auto-  Exceptions:
                       matically unlocks the door.                       1. A main exit of a Group A occupancy shall be per-
                    5. Where panic or fire exit hardware is required by     mitted to have locking devices in accordance
                       Section 1010.1.10, operation of the panic or fire    with Section 1010.1.9.4, Item 2.
                       exit hardware also releases the electric lock.    2. Doors provided with panic hardware or fire exit
                    6. The locking system units shall be listed in accor-   hardware and serving a Group A or E occupancy
                       dance with UL 294.                                   shall be permitted to be  electrically locked in