Page 204 - 2018_IFC
P. 204

MEANS OF EGRESS



                                                                                  1
               landings shall have a solid surface. Finish floor surfaces  not be more than 9 /  inches (241 mm). The minimum stair-
                                                                                   2
               shall be securely attached.                        way clear width at and below the handrail shall be 26 inches
                  Exceptions:                                     (660 mm).
                    1. Openings in stair walking surfaces shall be a size  [BE] 1011.11 Handrails.  Flights of  stairways shall have
                                                   1
                       that does not permit the passage of  / -inch-diam-  handrails on each side and shall comply with Section 1014.
                                                    2
                       eter (12.7 mm) sphere. Elongated openings shall  Where  glass  is used to provide the  handrail, the  handrail
                       be placed so that the long dimension is perpen-  shall comply with Section 2407 of the International Building
                       dicular to the direction of travel.        Code.
                    2. In Group F,  H and S  occupancies, other  than  Exceptions:
                       areas of parking structures accessible to the pub-  1. Flights of  stairways within  dwelling units, and
                       lic, openings in treads and landings shall not be  flights of  spiral  stairways are permitted to have a
                       prohibited provided that a sphere with a diameter  handrail on one side only.
                          1
                       of 1 /  inches (29 mm) cannot pass through the  2. Decks, patios and walkways that have a single
                           8
                       opening.                                          change in elevation where the landing depth on each
               [BE] 1011.7.2 Outdoor conditions.  Outdoor  stairways     side of the change of elevation is greater than what
               and outdoor approaches to stairways shall be designed so  is required for a landing do not require handrails.
               that water will not accumulate on walking surfaces.     3. In Group R-3 occupancies, a change in elevation
               [BE] 1011.7.3 Enclosures under interior stairways. The    consisting of a single riser at an entrance or egress
               walls and soffits within  enclosed usable spaces under    door does not require handrails.
               enclosed and unenclosed stairways shall be protected by  4. Changes in room elevations of three or fewer risers
               1-hour fire-resistance- rated construction or the fire-resis-  within dwelling units and sleeping units in Group R-
               tance rating of  the  stairway enclosure, whichever is    2 and R-3 do not require handrails.
               greater. Access to the enclosed space shall not be directly
               from within the stairway enclosure.                [BE] 1011.12 Stairway to roof. In buildings four or more
                                                                  stories above grade plane, one stairway shall extend to the
                  Exception:  Spaces under  stairways  serving and con-  roof surface, unless the roof has a slope steeper than four
                  tained within a single residential dwelling unit in Group  units vertical in 12 units horizontal (33-percent slope).
                  R-2 or R-3 shall be permitted to be protected on the
                                 1
                  enclosed side with  / -inch (12.7 mm) gypsum board.  Exception: Other than where required  by  Section
                                  2
                                                                     1011.12.1, in buildings without an occupied roof, access to
               [BE] 1011.7.4 Enclosures under exterior stairways.    the roof from the top story shall be permitted to be by an
               There shall not be enclosed usable space under  exterior  alternating tread device, a ships ladder or a permanent
               exit stairways unless the space is completely enclosed in  ladder.
               1-hour fire-resistance-rated construction. The open space
               under exterior stairways shall not be used for any purpose.  [BE] 1011.12.1 Stairway to elevator equipment. Roofs
                                                                     and penthouses containing elevator equipment that must
             [BE] 1011.8 Vertical rise. A flight of stairs shall not have a  be accessed for maintenance are required to be accessed
             vertical rise greater than 12  feet (3658 mm) between floor  by a stairway.
             levels or landings.
                                                                     [BE] 1011.12.2  Roof access. Where  a  stairway is  pro-
               Exception:  Spiral  stairways used as a  means of  egress  vided  to a roof, access to the roof  shall be provided
               from technical production areas.                      through a penthouse complying with Section 1510.2 of the
             [BE] 1011.9  Curved stairways. Curved  stairways with   International Building Code.
             winder treads shall have treads and risers in accordance with  Exception: In buildings without an occupied roof,
             Section 1011.5 and the smallest radius shall be not less than  access to the roof shall be permitted to be a roof hatch
             twice the minimum width or required capacity of the stair-  or trap door not less than 16 square feet (1.5 m ) in area
                                                                                                            2
             way.                                                      and having a minimum dimension of 2 feet (610 mm).
               Exception: The radius restriction shall not apply to curved  [BE] 1011.13 Guards. Guards shall be provided along stair-
               stairways in Group  R-3 and within  individual  dwelling  ways and landings where required by Section 1015 and shall
               units in Group R-2.                                be constructed in accordance with Section 1015. Where the
             [BE] 1011.10 Spiral stairways. Spiral stairways are permit-  roof hatch opening providing the required access is located
             ted to be used as a component in the means of egress only  within 10 feet (3049 mm) of the roof edge, such roof access
             within  dwelling units or from a space not more than 250  or roof edge shall be protected by guards installed in accor-
                            2
             square feet (23 m ) in area and serving not more than five  dance with Section 1015.
             occupants, or from technical production areas in accordance  [BE] 1011.14 Alternating tread devices. Alternating tread
             with Section 410.5 of the International Building Code.  devices  are  limited to an element  of a  means of  egress in
                                          3
               A spiral stairway shall have a 6 / -inch (171 mm) mini-  buildings of Groups F, H and S from a mezzanine not more
                                           4
                                                                                        2
             mum clear tread depth at a point 12 inches (305 mm) from the  than 250 square feet (23 m ) in area and that serves not more
             narrow edge. The risers shall be sufficient to provide a head-  than five occupants; in buildings of Group I-3 from a guard
             room of 78 inches (1981 mm) minimum, but riser height shall  tower, observation station or control room not more than 250

             2018 INTERNATIONAL FIRE CODE ®                                                                      171
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.