Page 207 - 2018_IFC
P. 207

MEANS OF EGRESS



                openings into seating areas where exit signs are pro-  to an emergency power system provided from storage bat-
                vided in the concourse that are readily apparent from  teries, unit equipment or an on-site generator. The installa-
                the vomitories. Egress lighting is provided to iden-  tion of the emergency power system shall be in accordance
                tify each vomitory or opening within the seating  with Section 604. Group I-2, Condition 2 exit sign illumi-
                area in an emergency.                            nation shall not be provided by unit equipment batteries
         [BE] 1013.2 Floor-level exit signs in Group R-1. Where  only.
         exit signs are required in Group R-1 occupancies by Section  Exception: Approved exit sign illumination types that
         1013.1, additional low-level exit signs shall be provided in all  provide continuous illumination independent of exter-
         areas serving guestrooms in Group R-1 occupancies and shall  nal power sources for a  duration of not less than 90
         comply with Section 1013.5.                               minutes, in case of primary power loss, are not required
           The bottom of the sign shall be not less than 10 inches  to be connected to an emergency electrical system.
         (254 mm) nor more than 18 inches (455 mm) above the floor
         level.  The sign shall be flush mounted to the door or wall.           SECTION 1014
         Where mounted  on  the wall, the  edge  of the sign shall be             HANDRAILS
         within 4 inches (102 mm) of the door frame on the latch side.
                                                              [BE] 1014.1 Where required. Handrails serving flights of
         [BE] 1013.3 Illumination. Exit signs shall be internally or
         externally illuminated.                              stairways, ramps, stepped aisles and ramped aisles shall be
                                                              adequate in strength and attachment in accordance with Sec-
           Exception: Tactile signs required by Section 1013.4 need  tion 1607.8 of the  International Building Code.  Handrails
           not be provided with illumination.
                                                              required for  flights of  stairways by Section 1011.11 shall
         [BE] 1013.4 Raised character and braille exit signs. A sign  comply with Sections 1014.2 through 1014.9.  Handrails
         stating EXIT  in visual characters, raised characters and  required for ramps by Section 1012.8 shall comply with Sec-
         braille and complying with ICC  A117.1 shall be provided  tions 1014.2 through 1014.8. Handrails for stepped aisles and
         adjacent to each door to an area of refuge providing direct  ramped aisles required by Section 1029.16 shall comply with
         access to a stairway, an exterior area for assisted rescue, an  Sections 1014.2 through 1014.8.
         exit stairway or ramp, an exit passageway and the exit dis-  [BE] 1014.2 Height. Handrail height, measured above stair
         charge.                                              tread nosings, or finish surface of ramp slope, shall be uni-
         [BE] 1013.5 Internally illuminated exit signs. Electrically  form, not less than 34 inches (864 mm) and not more than 38
         powered, self-luminous and photoluminescent exit signs shall  inches (965  mm).  Handrail  height of  alternating tread
         be listed and labeled in accordance with UL 924 and shall be  devices  and ships ladders, measured above tread  nosings,
         installed in accordance with the manufacturer’s instructions  shall be uniform, not less than 30 inches (762 mm) and not
         and Section 1203. Exit signs shall be illuminated at all times.  more than 34 inches (864 mm).
         [BE] 1013.6 Externally illuminated exit signs. Externally  Exceptions:
         illuminated exit signs shall comply with Sections 1013.6.1  1.  Where handrail fittings or bendings are used to pro-
         through 1013.6.3.
                                                                     vide continuous transition between  flights, the fit-
           [BE] 1013.6.1 Graphics. Every exit sign and directional   tings or bendings shall be permitted to exceed the
           exit sign shall have plainly legible letters not less than 6  maximum height.
           inches (152 mm) high with the principal strokes of the let-  2. In Group R-3 occupancies; within dwelling units in
                           3
           ters not  less than  /   inch (19.1 mm) wide. The word    Group R-2 occupancies; and in Group U occupan-
                             4
           “EXIT” shall have letters having a width not less than 2  cies that are associated with a Group R-3 occupancy
           inches (51 mm) wide, except the letter “I,” and the mini-  or associated  with individual  dwelling units in
                                                    3
           mum spacing between letters shall be not less than  /  inch  Group R-2  occupancies; where handrail fittings  or
                                                      8
           (9.5 mm). Signs larger than the minimum established in    bendings are used to provide continuous transition
           this section shall have letter widths, strokes and spacing in  between  flights, transition at  winder treads,  transi-
           proportion to their height.
                                                                     tion from handrail to  guard,  or where used at the
              The word “EXIT” shall be in high contrast with the     start of a flight, the handrail height at the fittings or
           background  and shall be  clearly  discernible when the   bendings shall be permitted to exceed the maximum
           means of exit sign illumination is or is not energized. If a  height.
           chevron directional indicator is provided as part of the exit  3. Handrails on top of a guard where permitted along
           sign, the construction shall be such that the direction of the  stepped aisles and ramped aisles in accordance with
           chevron directional indicator cannot be readily changed.
                                                                     Section 1029.16.
           [BE] 1013.6.2 Exit sign illumination. The face of an exit  [BE] 1014.3  Handrail graspability. Required  handrails
           sign illuminated from an external source shall have an  shall comply with Section 1014.3.1 or shall provide equiva-
           intensity of not less than 5 foot-candles (54 lux).
                                                              lent graspability.
           [BE] 1013.6.3 Power source. Exit signs shall be illumi-  Exception:  In Group R-3 occupancies; within  dwelling
           nated at all times. To ensure continued illumination for a  units in Group R-2 occupancies; and in Group U occupan-
           duration of not less than 90 minutes in case of primary  cies that are accessory to a Group R-3 occupancy or acces-
           power loss, the sign illumination means shall be connected
                                                                 sory to individual  dwelling units in  Group R-2

         174                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   202   203   204   205   206   207   208   209   210   211   212