MEANS OF EGRESS



                  6. Within individual dwelling units and sleeping units  fully open, shall not reduce the minimum net clear open-
                    in Group R-2 and R-3 occupancies, guards on the  ing area of the window unit to less than the area required
                    open sides of  stairs  shall not have openings that  by Section 1030.2.
                                           3
                    allow passage of a sphere 4 /  (111 mm) inches in
                                             8
                    diameter.
                                                                                    SECTION 1016
             [BE]  1015.5 Screen porches.  Porches and  decks that are               EXIT ACCESS
             enclosed with insect screening shall be provided with guards
             where the walking surface is located  more than 30 inches  [BE] 1016.1 General. The exit access shall comply with the
             (762 mm) above the floor or grade below.             applicable provisions  of  Sections 1003 through 1015.  Exit
                                                                  access arrangement shall comply with Sections 1016 through
             [BE] 1015.6 Mechanical equipment, systems and devices.
             Guards  shall  be provided where various components  that  1021.
             require service are located within 10 feet (3048 mm) of a roof  [BE] 1016.2  Egress through  intervening spaces.  Egress
             edge or open side of a walking surface and such edge or open  through intervening spaces shall comply with this section.
             side is located more than 30 inches (762 mm) above the floor,  1. Exit access through an enclosed elevator lobby is per-
             roof or grade below. The guard shall extend not less than 30  mitted. Access to not less than one of the required exits
             inches (762 mm) beyond each end of such components. The   shall be provided without travel through the enclosed
             guard shall be constructed so as to prevent the passage of a  elevator lobbies required by Section 3006 of the Inter-
             sphere 21 inches (533 mm) in diameter.                    national Building Code. Where the path of exit access
               Exception: Guards are not required where personal  fall  travel passes through an enclosed elevator lobby the
               arrest  anchorage connector devices  that comply  with  level of protection required for the enclosed elevator
               ANSI/ASSE Z 359.1 are installed.                        lobby is not required to be extended to the exit unless
                                                                       direct access to an exit is required by other sections of
             [BE] 1015.7 Roof access. Guards shall be provided where
             the roof hatch opening is located within 10 feet (3048 mm) of  this code.
             a roof edge or open side of a walking surface and such edge  2. Egress from a room or space shall not pass through
             or open side is located more than 30 inches (762 mm) above  adjoining or intervening rooms or areas, except where
             the floor, roof or grade below. The guard shall be constructed  such adjoining rooms or areas and the area served are
             so as to prevent the passage of a sphere 21 inches (533 mm)  accessory to one or the other, are not a Group H occu-
             in diameter.                                              pancy and provide a discernible path of egress travel to
                                                                       an exit.
               Exception: Guards are not required where personal  fall
               arrest  anchorage connector devices  that comply with     Exception:  Means of  egress  are not prohibited
               ANSI/ASSE Z 359.1 are installed.                          through adjoining or intervening rooms or spaces in
                                                                         a Group H, S or F occupancy where the adjoining or
             [BE] 1015.8 Window openings. Windows in Group R-2 and
             R-3 buildings including dwelling units, where the top of the  intervening rooms or spaces are the same or a lesser
             sill of an operable window opening is located less than 36  hazard occupancy group.
             inches above the finished  floor and more than 72 inches  3. An exit access shall not pass through a room that can be
             (1829 mm) above the finished grade or other surface below  locked to prevent egress.
             on the exterior of the building, shall comply with one of the  4. Means of egress from dwelling units or sleeping areas
             following:                                                shall not lead through other sleeping areas, toilet rooms
               1. Operable windows where the top of the sill of the open-  or bathrooms.
                  ing is located more than 75 feet (22 860 mm) above the  5. Egress shall not pass through kitchens, storage rooms,
                  finished grade or other surface below and that are pro-  closets or spaces used for similar purposes.
                  vided with window fall prevention devices that comply  Exceptions:
                  with ASTM F2006.
                                                                            1. Means of egress are not prohibited through a
               2. Operable windows where the openings will not allow a        kitchen area serving  adjoining  rooms consti-
                  4-inch-diameter (102 mm) sphere to pass through the         tuting part of the same dwelling unit or sleep-
                  opening when the window is in its largest opened posi-
                                                                              ing unit.
                  tion.
                                                                            2. Means of egress  are not prohibited through
               3. Operable windows  where  the openings are provided          stockrooms in Group M occupancies where all
                  with window fall prevention devices that comply with
                                                                              of the following are met:
                  ASTM F2090.
                                                                                 2.1. The stock is of the same hazard classi-
               4. Operable  windows that are  provided with window
                  opening control  devices that comply with  Section                fication as that found in the main retail
                                                                                    area.
                  1015.8.1.
                                                                                 2.2. Not more than 50 percent of the exit
               [BE]  1015.8.1  Window opening control devices. Win-
               dow opening control devices shall comply with ASTM                   access is through the stockroom.
               F2090. The window opening control device, after opera-            2.3. The stockroom is not subject to lock-
               tion to release the control device allowing the window to            ing from the egress side.

             2018 INTERNATIONAL FIRE CODE ®                                                                      177
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.