MEANS OF EGRESS



                       2.4. There is a demarcated, minimum 44-   exit access stairway or the closest slope of an exit access
                           inch-wide (1118 mm) aisle defined by  ramp.
                           full- or partial-height fixed walls or  [BE] 1017.3.1 Exit access stairways and ramps. Travel
                           similar construction that will maintain  distance on  exit access stairways or  ramps shall be
                           the required width and lead directly  included in the exit access  travel distance measurement.
                           from the retail area to the exit without
                           obstructions.
           [BE] 1016.2.1 Multiple tenants.  Where more than one
           tenant occupies any one floor of a building or structure,
           each tenant space, dwelling unit and sleeping unit shall be         [BE] TABLE 1017.2
           provided with access to the required exits without passing     EXIT ACCESS TRAVEL DISTANCE a
           through adjacent tenant spaces, dwelling units and sleep-           WITHOUT SPRINKLER   WITH SPRINKLER
           ing units.                                             OCCUPANCY         SYSTEM          SYSTEM
                                                                                     (feet)          (feet)
              Exception: The means of egress from a smaller tenant  A, E, F-1, M, R, S-1  200        250 b, e
              space shall not be prohibited from passing through a                                      b
              larger adjoining  tenant  space where such  rooms or  I-1           Not Permitted       250
              spaces of the smaller tenant occupy less than 10 percent  B            200              300 c
              of the area of the larger tenant space through which  F-2, S-2, U      300              400 c
              they pass; are the same or similar occupancy group; a  H-1          Not Permitted       75 d
              discernable path of egress travel to an exit is provided;                                 d
              and the means of egress into the adjoining space is not  H-2        Not Permitted       100
              subject to locking  from the egress side. A required  H-3           Not Permitted       150 d
              means of egress  serving the larger tenant space shall  H-4         Not Permitted       175 d
              not pass through the smaller tenant space or spaces.  H-5           Not Permitted       200 c
                                                              I-2, I-3            Not Permitted       200 c
                           SECTION 1017                       I-4                    150              200 c
                  EXIT ACCESS TRAVEL DISTANCE                 For SI: 1 foot = 304.8 mm.
         [BE] 1017.1 General. Travel distance within the exit access  a. See the following sections for modifications to exit access travel distance
         portion of the means of egress system shall be in accordance  requirements:
         with this section.                                      Section 402.8 of the  International Building  Code: For  the distance
                                                                   limitation in malls.
         [BE] 1017.2  Limitations.  Exit access travel  distance shall  Section 404.9 of the  International Building  Code: For  the distance
         not exceed the values given in Table 1017.2.              limitation through an atrium space.
                                                                 Section 407.4 of the  International Building  Code: For  the distance
           [BE]  1017.2.1 Exterior egress balcony  increase.  Exit  limitation in Group I-2.
           access travel distances specified in Table 1017.2 shall be  Sections 408.6.1 and 408.8.1 of the International Building Code: For the
           increased up to an additional 100 feet (30 480 mm) pro-  distance limitations in Group I-3.
           vided that the last portion of the exit access leading to the  Section 411.3 of the  International Building  Code: For  the distance
           exit occurs on an exterior egress balcony constructed in  limitation in special amusement buildings.
           accordance with Section 1021. The length of such balcony  Section 412.6 of the  International Building  Code: For  the distance
           shall be not less than the amount of the increase taken.   limitations in aircraft manufacturing facilities.
                                                                 Section  1006.2.2.2: For the distance  limitation in refrigeration
           [BE] 1017.2.2 Groups F-1 and S-1 increase. The maxi-    machinery rooms.
           mum exit access travel distance shall be 400 feet (122 m)  Section 1006.2.2.3: For the distance limitation in refrigerated rooms and
           in Group F-1 or S-1 occupancies where all of the follow-  spaces.
           ing conditions are met:                               Section 1006.3.3: For buildings with one exit.
                                                                 Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1.
              1. The portion of the building classified as Group F-1  Section 1029.7: For increased limitation in assembly seating.
                or S-1 is limited to one story in height.        Section 3103.4 of the  International Building Code: For temporary
              2. The minimum height from the finished floor to the  structures.
                bottom of the ceiling or roof slab or deck is 24 feet  Section 3104.9 of the  International Building Code: For pedestrian
                (7315 mm).                                         walkways.
                                                              b. Buildings equipped throughout  with  an automatic sprinkler system  in
              3. The building is equipped throughout with an auto-  accordance  with Section  903.3.1.1  or  903.3.1.2. See Section 903  for
                matic sprinkler  system in  accordance with  Section  occupancies where automatic sprinkler systems are permitted in
                903.3.1.1.                                      accordance with Section 903.3.1.2.
                                                              c. Buildings equipped throughout  with  an automatic sprinkler system  in
         [BE] 1017.3 Measurement. Exit access travel distance shall  accordance with Section 903.3.1.1.
         be measured from the most remote point of each room, area  d. Group H occupancies equipped  throughout with an  automatic  sprinkler
         or space along the natural and unobstructed path of horizontal  system in accordance with Section 903.2.5.1.
         and vertical egress travel to the entrance to an exit.  e. Group R-3 and R-4 buildings  equipped throughout with an automatic
                                                                sprinkler system  in accordance  with Section  903.3.1.3. See Section
           Exception: In open parking garages, exit access travel dis-  903.2.8 for occupancies where automatic sprinkler systems are permitted
           tance is permitted to be measured to the closest riser of an  in accordance with Section 903.3.1.3.