FLAMMABLE AND COMBUSTIBLE LIQUIDS



                                                                                     2
              5704.2.8.12 Liquid removal. Means shall be provided    square feet (139 m ), and is in accordance with one
              to recover liquid from the vault. Where a pump is used  of the following:
              to meet this requirement, the pump shall not be perma-    1. Used for the storage of Class I or II liquids.
              nently installed in the vault. Electric-powered portable
              pumps shall be suitable for use in Class I, Division 1, or  2. Used for the storage of crude oil.
              Zone 0 locations, as defined in NFPA 70.                  3. Used for  in-process products  and is located
              5704.2.8.13 Normal vents. Vent pipes that are pro-          within 100 feet (30 480 mm) of a fired still,
              vided for normal tank venting shall terminate not less      heater, related fractioning or processing appa-
              than 12 feet (3658 mm) above ground level.                  ratus or similar device at a processing plant or
                                                                          petroleum refinery as herein defined.
              5704.2.8.14 Emergency vents. Emergency vents shall
              be vapor tight and shall be allowed to discharge inside   4. Considered by the fire code official as posing
              the  vault. Long-bolt manhole covers shall  not  be         an unusual exposure hazard because of topo-
              allowed for this purpose.                                   graphical conditions; nature of occupancy,
                                                                          proximity on the same or adjoining property,
              5704.2.8.15 Accessway. Vaults shall be provided with        and height and character of liquids to be
              an  approved personnel  accessway with a minimum            stored; degree of private fire protection to be
              dimension of 30 inches (762 mm) and with a perma-           provided; and facilities of the fire department
              nently affixed, nonferrous ladder. Accessways shall be      to cope with flammable liquid fires.
              designed to be nonsparking. Travel distance from any
              point inside a vault to an accessway shall not exceed 20  5704.2.9.2.2 Foam fire protection system installa-
              feet (6096 mm). At each entry point, a warning sign    tion. Where foam fire protection is required, it shall
              indicating the need for procedures for safe entry into  be installed in accordance with NFPA 11.
              confined spaces shall be posted. Entry points shall be    5704.2.9.2.2.1 Foam storage. Where foam fire
              secured against unauthorized entry and vandalism.         protection is required, foam-producing materials
              5704.2.8.16 Fire protection. Vaults shall be provided     shall be stored on the premises.
              with a suitable means to admit a fire suppression agent.    Exception: Storage of foam-producing materi-
              5704.2.8.17 Classified  area. The  interior of  a vault     als off the premises is allowed as follows:
              containing a tank that stores a Class I liquid shall be        1. Such materials stored  off  the premises
              designated a Class I, Division 1, or Zone 0 location, as         shall be of the proper type suitable for
              defined in NFPA 70.                                              use with  the equipment at the installa-
              5704.2.8.18 Overfill protection. Overfill protection             tion where required.
              shall be  provided in accordance with Section                  2. Such materials shall be readily available
              5704.2.9.7.5. The use of a float vent valve shall be pro-        at the storage location at all times.
              hibited.
                                                                             3. Adequate loading  and transportation
           5704.2.9 Above-ground tanks. Above-ground storage of                facilities shall be provided.
           flammable and combustible liquids in tanks shall comply
           with Section 5704.2 and  Sections 5704.2.9.1 through              4. The time required to deliver such mate-
           5704.2.9.7.9.                                                       rials to the required location in the event
                                                                               of fire shall be consistent with the haz-
              5704.2.9.1 Existing noncompliant  installations.                 ards and fire  scenarios for which  the
              Existing above-ground tanks shall be maintained in               foam supply is intended.
              accordance with the code requirements that were appli-
              cable at  the time of installation.  Above-ground tanks        5. At the time of a fire, these off-premises
              that were installed in violation of code  requirements           supplies shall be accumulated in suffi-
              applicable at the time of installation shall be made code        cient quantities before placing the
              compliant or shall be removed in accordance with Sec-            equipment in operation to  ensure foam
              tion  5704.2.14, regardless of whether such tank has             production at an adequate rate without
              been previously inspected (see Section 107.4).                   interruption until extinguishment  is
                                                                               accomplished.
              5704.2.9.2 Fire protection. Fire protection for above-
              ground tanks shall comply with Sections 5704.2.9.2.1   5704.2.9.2.3 Fire protection of supports. Supports
              through 5704.2.9.2.4.                                  or pilings for above-ground tanks storing Class I, II
                                                                     or IIIA liquids elevated more than 12 inches (305
                5704.2.9.2.1 Required foam fire protection sys-      mm) above grade shall have a fire-resistance rating
                tems. Where required by the fire code official, foam  of not less than 2 hours in accordance with the fire
                fire protection shall be provided for above-ground   exposure criteria specified in ASTM E1529.
                tanks, other than pressure tanks operating at or
                above  1  pound per square inch  gauge (psig)  (6.89    Exceptions:
                kPa) where such tank, or group of tanks spaced less       1. Structural supports tested as part of a pro-
                than 50 feet (15 240 mm) apart measured shell to             tected above-ground  tank in  accordance
                shell,  has a  liquid  surface  area in excess of 1,500      with UL 2085.