Page 461 - 2018_IFC
P. 461

FLAMMABLE AND COMBUSTIBLE LIQUIDS



                   within a diked area or drainage path for a tank or  5704.2.9.7 Additional requirements for protected
                   tanks storing Class I or II liquids. Where a Class  above-ground tanks. In addition to the requirements
                   IIIB liquid storage tank is within the diked area  of this chapter for above-ground tanks, the installation
                   or drainage path for a Class I or II liquid, dis-  of protected above-ground tanks shall be in accordance
                   tances required by Section 5704.2.9.6.1.1 shall  with Sections 5704.2.9.7.1 through 5704.2.9.7.9.
                   apply.
                                                                     5704.2.9.7.1 Tank construction. The construction
                   5704.2.9.6.1.6 Reduction of separation dis-       of  a protected above-ground  tank and its  primary
                   tances to adjacent property. Where two tank       tank shall be in accordance with Section 5704.2.7.
                   properties of diverse ownership have a common
                   boundary, the fire code official is authorized to,  5704.2.9.7.2 Normal and emergency venting. Nor-
                   with the written consent of the owners of the two  mal and emergency venting  for protected above-
                   properties,  apply the distances in  Sections     ground tanks shall be provided in accordance with
                   5704.2.9.6.1.2 through 5704.2.9.6.1.5 assuming a  Sections 5704.2.7.3 and 5704.2.7.4. The vent capac-
                   single property.                                  ity reduction factor shall not be allowed.
                5704.2.9.6.2 Separation between adjacent stable      5704.2.9.7.3 Secondary  containment. Protected
                or unstable liquid tanks. The separation between     above-ground tanks shall be provided with second-
                tanks containing  stable liquids shall be in accor-  ary containment, drainage control or diking in accor-
                dance with Table 22.4.2.1 of NFPA 30. Where tanks    dance with  Section 5004.2. A means shall be
                are in a diked area containing Class I or II liquids, or  provided to establish the integrity of the secondary
                in the drainage path of Class I or II liquids, and are  containment in accordance with NFPA 30.
                compacted in three or more rows or in an irregular   5704.2.9.7.4 Vehicle impact protection. Where
                pattern, the fire code official is authorized to require  protected above-ground tanks, piping, electrical con-
                greater separation than specified in Table 22.4.2.1 of  duit or dispensers are subject to vehicular impact,
                NFPA 30 or other means to make tanks in the inte-
                rior of the pattern open for fire-fighting purposes.  they shall be protected therefrom, either by having
                                                                     the impact protection incorporated into the system
                   The separation between tanks containing unsta-    design in compliance with the impact test protocol
                ble liquids shall be not less than one-half the sum of  of UL 2085, or by meeting the provisions of Section
                their diameters.
                                                                     312, or  where necessary, a combination of both.
                   Exception: Tanks used for storing Class IIIB liq-  Where guard posts or other  approved barriers  are
                   uids are allowed to be spaced 3 feet (914 mm)     provided, they shall be independent of each above-
                   apart unless within a diked area or drainage path  ground tank.
                   for a tank storing Class I or II liquids.
                                                                     5704.2.9.7.5 Overfill prevention. Protected above-
                5704.2.9.6.3 Separation between adjacent tanks       ground tanks shall not be filled in excess of 95 per-
                containing flammable or combustible liquids and      cent of their capacity. An overfill prevention system
                LP-gas. The minimum  horizontal separation           shall be provided for each tank. During tank-filling
                between an LP-gas container and a Class I, II or IIIA
                liquid storage tank shall be 20 feet (6096 mm)       operations, the system shall comply with one of the
                except in the case of Class I, II or IIIA liquid tanks  following:
                operating at pressures exceeding 2.5 psig (17.2 kPa)    1. The  overfill prevention system  shall include
                or equipped with emergency venting allowing pres-         the following:
                sures to exceed 2.5 psig (17.2 kPa), in which case           1.1. An independent means of notifying the
                the provisions of Section 5704.2.9.6.2 shall apply.
                                                                                person  filling the tank  that the fluid
                   An approved means shall be provided to prevent               level has reached  90 percent of tank
                the accumulation of Class I, II or IIIA liquids under           capacity by  providing an audible  or
                adjacent LP-gas containers such as by dikes, diver-             visual alarm signal, providing  a tank
                sion curbs or grading. Where flammable or combus-               level  gauge marked at 90  percent  of
                tible liquid storage tanks are within a diked area, the         tank capacity, or  other  approved
                LP-gas containers shall be outside the  diked area              means.
                and not less than 10 feet (3048 mm) away from the
                centerline of the wall of the diked area.                    1.2. Automatic shut off of the flow of fuel
                                                                                to the tank when the quantity of liquid
                   Exceptions:
                                                                                in the tank reaches 95 percent of tank
                     1. Liquefied petroleum gas containers of 125               capacity. For rigid  hose fuel-delivery
                       gallons (473 L) or less in capacity installed            systems, an  approved means shall be
                       adjacent to fuel-oil supply tanks of 660 gal-            provided to empty the fill hose into the
                       lons (2498 L) or less in capacity.
                                                                                tank after the automatic shutoff device
                     2. Horizontal separation is not required                   is activated.
                       between above-ground LP-gas containers           2. The system shall reduce the flow rate to not
                       and underground flammable and combusti-            more than 15 gallons per minute (0.95 L/s) so
                       ble liquid tanks.
                                                                          that at the reduced flow rate, the tank will not
                                                                          overfill for 30 minutes, and automatically shut


         428                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   456   457   458   459   460   461   462   463   464   465   466