FLAMMABLE AND COMBUSTIBLE LIQUIDS



                2. The distance from any part of a tank storing liq-  or  be removed in accordance with Section
                   uids to the nearest wall of a basement, pit, cellar  5704.2.14:
                   or lot line shall be not less than 3 feet (914 mm).  1. Flammable or  combustible liquids shall  be
                3. A minimum distance of 1 foot (305 mm), shell to        removed from the tank.
                   shell, shall be maintained between underground       2. All piping, including fill line, gauge opening,
                   tanks.                                                 vapor return and pump connection, shall  be
              5704.2.11.2 Depth and cover. Excavation for under-          capped or plugged and secured from tamper-
              ground storage tanks shall be made  with due  care to       ing.
              avoid undermining of  foundations  of existing struc-     3. Vent lines shall remain open and be main-
              tures. Underground tanks shall be set on firm founda-       tained in accordance with Sections 5704.2.7.3
              tions and surrounded with not less than 6 inches (152       and 5704.2.7.4.
              mm) of noncorrosive inert material, such as clean sand.
                                                                     5704.2.13.1.3 Out of service for one year. Under-
              5704.2.11.3 Overfill protection and prevention sys-    ground tanks that  have been out of service for a
              tems. Fill pipes shall be equipped with a spill container  period of one year shall be removed from the ground
              and an overfill prevention system in accordance with   in accordance with Section 5704.2.14 or abandoned
              NFPA 30.
                                                                     in place in accordance with Section 5704.2.13.1.4.
              5704.2.11.4 Leak prevention. Leak prevention for       5704.2.13.1.4  Tanks abandoned in place. Tanks
              underground tanks shall comply with  Sections          abandoned in place shall be as follows:
              5704.2.11.4.1 and 5704.2.11.4.2.
                                                                        1. Flammable and  combustible liquids shall be
                5704.2.11.4.1 Inventory  control. Daily inventory         removed from the tank and connected piping.
                records for underground storage tank systems shall
                be maintained.                                          2. The suction,  inlet, gauge, vapor  return and
                                                                          vapor lines shall be disconnected.
                5704.2.11.4.2 Leak detection. Underground storage
                tank systems  shall be provided with  an  approved      3. The tank shall  be  filled completely  with an
                method of leak detection from any component of the        approved inert solid material.
                system that is designed and installed in accordance     4. Remaining underground piping  shall  be
                with NFPA 30.                                             capped or plugged.
           5704.2.12 Testing. Tank testing shall comply with Sec-       5. A  record of tank size, location and date  of
           tions 5704.2.12.1 and 5704.2.12.2.                             abandonment shall be retained.
              5704.2.12.1 Acceptance testing. Prior to being placed     6. All exterior above-grade fill piping  shall be
              into service, tanks shall be tested in accordance with      permanently removed when tanks are aban-
              Section 21.5 of NFPA 30.                                    doned or removed.
              5704.2.12.2  Testing of underground  tanks. Before     5704.2.13.1.5 Reinstallation of underground
              being covered or placed in use, tanks and piping con-  tanks. Tanks that are to be reinstalled for flammable
              nected to underground tanks shall be tested for tight-  or combustible liquid service shall be in accordance
              ness in  the presence of the  fire code official. Piping  with this chapter, ASME Boiler and Pressure Vessel
              shall be tested in  accordance  with Section  5703.6.3.  Code (Section VIII),  API 12-P, API  1615,  UL 58
              The system  shall not be  covered until it has been    and UL 1316.
              approved.
                                                                   5704.2.13.2 Above-ground tanks. Above-ground
           5704.2.13 Abandonment and status of tanks. Tanks        tanks taken out of service shall comply with Sections
           taken out of service shall be removed in accordance with  5704.2.13.2.1 through 5704.2.13.2.3.
           Section 5704.2.14, or safeguarded in accordance with Sec-
           tions 5704.2.13.1 through 5704.2.13.2.3 and API 1604.     5704.2.13.2.1 Temporarily out of service. Above-
                                                                     ground tanks temporarily out of service shall have
              5704.2.13.1 Underground  tanks. Underground  tanks     all connecting lines isolated from the tank  and be
              taken out of service shall comply with  Sections       secured against tampering.
              5704.2.13.1.1 through 5704.2.13.1.5.
                                                                        Exception: In-place fire protection (foam) sys-
                5704.2.13.1.1 Temporarily out of service. Under-        tem lines.
                ground tanks temporarily out of service shall have
                the fill line, gauge opening, vapor return and pump  5704.2.13.2.2 Out of service  for 90  days. Above-
                connection secure  against tampering. Vent  lines    ground tanks not used for a period of 90 days shall be
                                                                     safeguarded in accordance with Section 5704.2.13.1.2
                shall remain open and be maintained in accordance
                with Sections 5704.2.7.3 and 5704.2.7.4.             or removed in accordance with Section 5704.2.14.
                5704.2.13.1.2 Out of service for 90 days. Under-        Exceptions:
                ground tanks not used for a period of 90 days shall       1. Tanks and containers connected to oil burn-
                be safeguarded in accordance with all the following          ers that are not in use during the warm sea-