FLAMMABLE AND COMBUSTIBLE LIQUIDS



                         off flow into the tank so that none of the fit-    graphical conditions,  nature of occupancy  and
                         tings on the top of the tank are exposed to        proximity to  buildings  on  the same or adjacent
                         product because of overfilling.                    property, capacity, and construction of proposed
                                                                            tanks and character of liquids to be stored, and
                       5704.2.9.7.5.1 Information signs. A permanent        nature and quantity of private and public fire pro-
                       sign shall be provided at the fill point for the     tection provided.
                       tank, documenting the filling procedure and the
                       tank calibration chart.                           2. Drainage control and diking is not  required for
                                                                            listed secondary containment tanks.
                         Exception:  Where climatic conditions are
                         such that the sign may be obscured by ice or  5704.2.10.1 Volumetric capacity. The volumetric
                         snow, or weathered beyond readability or oth-  capacity of the  diked area shall be not less  than  the
                         erwise impaired, said procedures and chart    greatest amount of liquid that can be released from the
                         shall be located in the office window, lock box  largest tank within the diked area. The capacity of the
                         or other area available to the person filling the  diked area enclosing more than one tank shall be calcu-
                         tank.                                         lated by deducting the volume of the tanks other than
                                                                       the largest tank below the height of the dike.
                       5704.2.9.7.5.2 Determination of available tank
                       capacity. The filling procedure shall require the  5704.2.10.2 Diked areas containing  two or more
                       person filling the tank to determine the gallonage  tanks. Diked areas containing two or more tanks shall
                       (literage) required to fill it to 90 percent of capac-  be subdivided in accordance with NFPA 30.
                       ity before commencing the fill operation.       5704.2.10.3 Protection of piping from exposure fires.
                    5704.2.9.7.6 Fill pipe  connections. The fill pipe  Piping shall not pass through adjacent diked areas or
                    shall be provided with a means for making a direct  impounding basins, unless  provided with  a sealed
                    connection to the tank vehicle’s fuel delivery hose  sleeve or otherwise protected from exposure to fire.
                    so that the delivery of fuel is not exposed to the open  5704.2.10.4 Combustible materials in diked areas.
                    air during the filling operation. Where any portion of  Diked areas shall be kept free from combustible materi-
                    the fill pipe exterior to the tank extends below the  als, drums and barrels.
                    level of the top of the tank, a check valve shall be  5704.2.10.5 Equipment, controls and piping in diked
                    installed in the fill pipe not more than 12 inches (305  areas. Pumps, manifolds and fire protection equipment
                    mm) from the fill hose connection.
                                                                       or controls shall not be located within diked areas or
                    5704.2.9.7.7 Spill containers. A spill container hav-  drainage basins or in a location where such equipment
                    ing a capacity of not less than 5 gallons (19 L) shall  and controls would be endangered by fire in the diked
                    be provided for each fill connection. For tanks with  area or drainage basin. Piping above ground shall be
                    a top fill connection, spill containers shall be non-  minimized and located as close as practical to the shell
                    combustible and shall be  fixed to the tank and    of the tank in diked areas or drainage basins.
                    equipped with a manual drain valve that drains into  Exceptions:
                    the primary tank. For tanks with a remote fill con-
                    nection, a portable spill container shall be allowed.   1. Pumps, manifolds and piping integral to the
                                                                              tanks or equipment being served, which is pro-
                    5704.2.9.7.8 Tank openings. Tank openings in pro-         tected by intermediate diking, berms, drainage
                    tected above-ground tanks shall be through the top        or fire protection such as water spray, moni-
                    only.                                                     tors or resistive coating.
                    5704.2.9.7.9 Antisiphon devices. Approved antisi-       2. Fire protection equipment or controls that are
                    phon devices shall be installed in each external pipe     appurtenances to the tanks or equipment being
                    connected to the protected above-ground tank where        protected, such as foam chambers or foam pip-
                    the pipe extends below the level of the top of the        ing and water or foam monitors and hydrants,
                    tank.                                                     or hand and wheeled extinguishers.
               5704.2.10 Drainage and diking. The area surrounding a  5704.2.11 Underground tanks. Underground storage of
               tank or group of tanks shall be provided with drainage  flammable and combustible liquids in tanks shall comply
               control or shall be diked to prevent accidental discharge of  with Section 5704.2 and  Sections 5704.2.11.1 through
               liquid  from endangering adjacent tanks,  adjoining  prop-  5704.2.11.4.2.
               erty or reaching waterways.
                                                                       5704.2.11.1 Location. Flammable and combustible liq-
                  Exceptions:                                          uid storage tanks located underground, either outside or
                                                                       under buildings, shall be in accordance with all of the
                    1. The  fire code official is authorized to alter or
                       waive these requirements based  on a technical  following:
                       report that demonstrates that such tank or group  1. Tanks shall be  located with  respect to existing
                       of tanks does not  constitute a hazard to  other     foundations and supports such that the loads car-
                       tanks,  waterways  or adjoining property, after      ried by the latter cannot  be transmitted  to  the
                       consideration  of special features such as topo-     tank.