Page 19 - DuraFlo™ 18 GPM Pump Station
P. 19

DURAFLO™ 18 GPM PUMPING STATIONS


                      Plumbing Overview


                      Pipe System Overview
                          Type M Copper
                                           1/2"       3/4"        1"        1-1/4"     1-1/2"      2"
                                         (13 mm)     (19 mm)   (25.4 mm)   (31.8 mm)   (38.1 mm)   (50.8 mm)
                              5 GPM      1.43/0.099
                             (18.9 LPM)   6.3/1.92
                              10 GPM      4.9/0.34   0.89/0.061
                             (37.8 LPM)   12.6/3.84   6.2/1.89
                              15 GPM     10.65/0.73   1.85/0.128   0.52/.036
                             (56.8 LPM)   19.9/6.066   9.3/2.84   5.5/1.68
                              20 GPM                 2.92/.2    0.87/.06
                             (75.7 LPM)              12.5/3.81   7.3/2.23
                              25 GPM                 4.32/.298   1.33/.092   0.49/.034
                             (94.6 LPM)
                                                     15.6/4.76   9.2/2.8   6.1/1.86
                              30 GPM                            1.81/.125   0.68/.047
                             (113.5 LPM)
                                                                 1.0/.31   7.3/2.23
                              40 GPM
                                                                3.04/.21   1.15/.079   0.51/.035
                             (151.4 LPM)
                                                                14.7/4.48   9.8/2.99   7.0/2.13
                                      Example                 PSI per 10 foot of pipe / BAR per 3 meters of pipe
                                                    4.16/.287
                                                    10.6/3.2   Velocity in feet per second / Velocity in meters per second

                             Note:  Velocity  should  not  exceed  15  feet  (4.6  meters)  per  second  in  a  correctly  installed
                                    system
                                           1/2"       3/4"        1"        1-1/4"     1-1/2"      2"
                                         (13 mm)     (19 mm)   (25.4 mm)   (31.8 mm)   (38.1 mm)   (50.8 mm)
                              Tee side    4 / 1.2     5 / 1.5    6 / 1.8    7 / 2.1    8 / 2.4    12 / 3.7
                               o
                              90 F Ell
                                          1-1/2 / .5   2 / .6   2-3/4 / .8   4 / 1.2   4 / 1.2    6 / 1.8
                             (23 C Ell)
                               o
                              45 F Ell    3/4 / .2    1 / .3    1-3/8 / .4   1-3/4 / .5   2 / .6   2-1/2 / .8
                               o
                             (11 C Ell)
                               o
                            Male/Female    1 / .3    1-1/2 / .5   2 / .6   2-3/4 / .8   3-1/2 / 1.1   4-1/2 / 1.4
                              Adapter
                                              Pressure loss, fittings (feet of pipe / meters of pipe)
                                                                       o
                                                                            o
                             Note:  All values calculated with clean water @ 60 F / 15 C



















                       1MANUL375         Belanger, Inc.® * PO BOX 5470 * Northville, MI 48167-5470* Ph (248) 349-7010 * Fax (248) 380-9681     15
   14   15   16   17   18   19   20   21   22   23   24