Page 21 - DuraFlo™ 18 GPM Pump Station
P. 21
DURAFLO™ 18 GPM PUMPING STATIONS
Plumbing Overview
Pipe System Overview
Hydraulic Hose
1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
(13 mm) (19 mm) (25.4 mm) (31.8 mm) (38.1 mm) (50.8 mm)
5 GPM 2.55/.176 0.88/.061
(18.9 LPM) 8.2/2.50 5.2/1.59
10 GPM 8.6/.593 2.98/.205 1.25/.086
(37.8 LPM) 16.3/4.97 10.5/3.2 7.3/2.23
15 GPM 6.06/.418 2.55/.176 0.65/.045
(56.8 LPM) 15.7/4.79 10.9/3.32 6.2/1.89
20 GPM 4.22/.291 1.07/.074
(75.7 LPM) 14.5/4.42 8.2/2.5
25 GPM 1.59/.110
(94.6 LPM)
10.2/3.11
30 GPM 2.18/.150 0.32/.022
(113.5 LPM)
12.3/3.75 5.4/1.65
40 GPM
3.61/.249 0.52/.036
(151.4 LPM)
16.3/4.97 7.3/2.23
Example PSI per 10 foot of pipe / BAR per 3 meters of pipe
4.16/.287
10.6/3.2 Velocity in feet per second / Velocity in meters per second
Note: Velocity should not exceed 15 feet (4.6 meters) per second in a correctly installed
system
1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
(13 mm) (19 mm) (25.4 mm) (31.8 mm) (38.1 mm) (50.8 mm)
Tee side 4 / 1.2 5 / 1.5 6 / 1.8 7 / 2.1 8 / 2.4 12 / 3.7
o
90 F Ell 1-1/2 / .5 2 / .6 2-3/4 / .8 4 / 1.2 4 / 1.2 6 / 1.8
(23 C Ell)
o
o
45 F Ell 3/4 / .2 1 / .3 1-3/8 / .4 1-3/4 / .5 2 / .6 2-1/2 / .8
o
(11 C Ell)
Male/Female 1 / .3 1-1/2 / .5 2 / .6 2-3/4 / .8 3-1/2 / 1.1 4-1/2 / 1.4
Adapter
Pressure loss, fittings (feet of pipe / meters of pipe)
o
o
Note: All values calculated with clean water @ 60 F / 15 C
1MANUL375 Belanger, Inc.® * PO BOX 5470 * Northville, MI 48167-5470* Ph (248) 349-7010 * Fax (248) 380-9681 17