Page 170 - FreeStyler® Maintenance Manual
P. 170

®
            MAINTENANCE


            Chapter 3 General Repairs


            Water Softener


               Solving the Problem

               Iron Bleed-Through – Applies to the Softener ONLY
                          Problem                     Reason                      Solution
                1.  Customer plumbing           Previous iron buildup inside      Verify that customer plumbing is
                                                 existing plumbing after the water   the problem by testing the water
                                                 softener                     quality at the brine fitting with water
                                                                              running
                2.  The water meter disc is not set      The composition of raw water can      Check the hardness and iron
                    properly for current raw water   change with time         content of raw water. Install the
                    conditions                                                correct disc for current raw water
                                                                              conditions
                3.  The salt setting is not set      The composition of raw water can      Check the hardness and iron
                    properly for current raw water   change with time         content of raw water. Set the brine
                    conditions                                                valve for current raw water
                                                                              conditions
                4.  The iron may be ferric iron      Ferric iron is not removable by ion      Colored water indicates ferritic
                                                 exchange                     state. If water is softened but has
                                                                              Iron Bleeding, it is most likely ferric
                                                The iron may be finer than the      Install a cartridge with finer micron
                                                 micron rating of the installed   rating
                                                 prefilter cartridge
                5.  The customer's plumbing may      A galvanized pressure tank will      Replace the galvanized pressure
                    include a galvanized pressure   create oxidized iron      tank with a bladder style pressure
                    tank                                                      tank

               Pressure Loss – Applies to the Filters and Distributors
                          Problem                     Reason                      Solution
                1.  Reduced pressure entering the      The pre-filter is clogged      Replace the clogged pre-filter
                    unit
                2.  The upper and/or lower      Foreign matter from the input lines      Clean the distributors. Add a pre-
                    distributors are plugged     is accumulating in the distributors   filter to eliminate the foreign matter
                                                                              before it enters the unit *

               Backwash Filters and Quad Filters/Softeners – Applies to Media Beds and Drain
                          Problem                     Reason                      Solution
                1.  Media bed may be fouled      The unit may not be backwashing      Clean up media beds and go to a
                                                 often enough due to changed   higher meter disc
                                                 water conditions or selection of too
                                                 low a meter disc
                2.  Flint gravel underbed may have      The unit may have been laid on its      Re-bed the unit
                    shifted                      side during shipment or installation
                3.  Drain flow is less than what is      Backwash flow control plugged      Clean backwash flow control
                    listed in the specifications or      Drain line is restricted      Clear any obstructions in drain line
                    media beds may not be getting
                    backwashed properly