Page 18 - LESSONS LEARNED BY MADARFM
P. 18
REAL TIME ISSUES (BURJ RAFAL TOWER)
Concern Area Issue Cause Risk Impact on Customer
2.Smoke Detection B. Earth fault from Heat No heat shrink tube Device will not be active Customer Loyalty
and Fire Alarm detector that is installed used for the connector incase of an emergency. Customer Damage
System inside the kitchen area. which in turn touches Brand Damage
with the aluminum Reputation Damage
ceiling installed inside Severe Injuries
the kitchen area
causing earth fault.
Ensure any modification to
existing international decorations
are approved by owner, and
smoke detector and fire alarm
system are insulated and
verified after work completed.
Note: This must be completed
by approved specialist sub-
contractor
18