                       Symptom              Possible Cause            Diagnostics                Action
                                          Steam in the cooling    • Fluid reservior is
                                          system is condensed                             • Replace the
                                                                    overly saturated.
                  During operation, the in the expansion                                    condenser.
                                                                  • Steam is
                  pressure at the low     valve hole and the                              • Discharge the
                                                                    condensed in the
                  end is sometimes        return pipe stops                                 steam inside the
                                                                    expansion valve
                  vacuum, and is          working from time to      hole and blocks the     return pipe.
                  normal in other times time. When it is                                  • Add some
                                                                    flow of the
                                          melted, it returns to                             refrigerant.
                                                                    refrigerant.
                                          normal.

                 •      Insufficient cooling (condition: ineffective cooling system)



























                       Symptom              Possible Cause            Diagnostics                Action

                  Vaccum at the low       • System leakage -      System leakage -        • Check the
                  end and low pressure      check connector
                                                                  insufficient              expansion valve.
                  at the high end. Frost    and exposed parts.
                  or dew on the pipes     • The flow of the       refrigerant, unable to • Blow off the dirt
                  before and after the      refrigerant is        circulate.                inside the