Page 1 - GVA Northwest
P. 1
Tyson Foods Proposal No. Q09526
1610 Midland Blvd.
Fort Smith, AR 72901 Date: March 12, 2014
Attention: Mr. Gerald Damron Salesman: DGB/kr
E-mail: gerald.damron@tyson.com Tel: 479-259-5987
We are pleased to quote the following, Fully Factory Packaged Model DC 2200S DIRECT
CONTACT WATER HEATER with Integral 520 Gallon Tank and Hot Water Delivery Pump
System, to be installed by the purchaser. This system is designed on the basis of the
information supplied to us by your plant to handle the following approximate quantities and
temperatures and produce the stated results.
CUSTOMER REQUIREMENTS:
Hot Water ---------------------------------------------- 1,800 GPH (30 GPM @ 180 Deg. F.)
Cold Water ---------------------------------------------------------------------------- 60 Deg. F.
Natural Gas Pressure (1000 Btu/Cubic Ft) -------------------- 1 PSIG @ 2,200 FT /Hr.
3
HEATER CAPACITY:
Direct Contact Water Heater (Patent No. 4574775) is rated at 2,200,000 BTU/HR and is capable
of heating 35 GPM from 60 to 180 Deg. F. at sea level to 1,000 foot elevation.
ESTIMATED ANNUAL VALUE OF HEAT LOAD REDUCTION:
Based upon heating 1,800 GPH of water from 60 to 180 Deg. F., 30 hours per week for 52 weeks
per year, and natural gas at a cost of $6.50 per thousand cubic feet, the annual cost reduction
would be $7,635.00 when compared to a conventional gas-fired heater or boiler system
operating at 70% system efficiency.
LUDELL EXTENDED WARRANTEE:
Ludell warrants its water heaters against defects in material and workmanship, under normal
use and service for a period of five (5) years after shipment for the fabricated stainless steel shell
and one (1) year for all other components. Ludell's obligation is limited to repair or replacement
f.o.b. Ludell's plant. Please note that customer supplied water chemistry may adversely effect
the equipment materials of construction. If the water supply is aggressive, acidic or high in
chlorides a higher-grade stainless steel alloy must be utilized. Contact Ludell for a quote
revision if your supply water chemistry is of poor quality.