                            5.      Prepiped and prewired pilot gas train assembly including:

                                    5.1    Pilot solenoid valve.
                                    5.2    Pilot pressure regulator.
                                    5.3    Pilot shutoff valve.
                                    5.4    Spark ignition assembly.
                                    5.5    Stable blast flame assembly.

                            6.      System mounted prewired U. L. Labeled control panel including:

                                    6.1    NEMA-12 enclosure.
                                    6.2.   Electronic temperature controller.
                                    6.3    Three (3) flush mounted digital thermometers indicating inlet
                                           water, outlet water and stack temperatures.
                                    6.4    Indicator light display panel.
                                    6.5    Audible alarm for water status (Bell).
                                    6.6    Numbered terminal strip for ease of hook-up.

                            7.      Microprocessor based burner management control system (U.L. Listed)
                                    including:

                                    7.1    Flame monitor.
                                    7.2    U.V. flame scanner.
                                    7.3    Diagnostic status display.
                                    7.4    Burner control panel.
                                    7.5    Audible alarm of burner status (Siren).

                            8.      Full thermostatic modulation control system including:

                                    8.1    Temperature sensors.
                                    8.2    Modulating drive motor.

                            9.      One (1) Sight glass to view combustion.


               One (1)      High Capacity Centrifugal Delivery Type Water Pump, capable of nominally
                            pumping 60 GPM at 115’ TDH. (50 PSIG), including:

                            1.      Bronze fitted with mechanical seals.
                            2.      Built together type configuration.
                            3.      Totally enclosed fan cooled electric motor, 5 Hp.