Page 394 - Maxwell House
P. 394

374                                                                Chapter 7


                           1
        shown in Figure 7.3.2a . If you have one of them, the measurement of S-parameters might be
        fun. Figure 7.3.2b illustrates schematically one of the possible setup to measure S-parameters
                                      2
        of two-port Device Under Test (DUT)  using NA. The RF sweep generator produces an incident
        wave signal with a time-varying frequency of the desired waveform. The complex magnitude 
                                                                                   1
        is controlled and measured by the highly sensitive power and phase meter   connected
        through the above-mentioned directional coupler. The latter is typically a  four-port device
        serves as a “traffic controller” directing a tiny portion of the incident power to the calibrated
        coupled  port with  power meter   and leaving the additional coupled port with dummy
        load (shown as resistor) isolated. Assume that the internal and high-speed RF switch is kept in
        position 1 during some short time period. If so, the incident wave   of known magnitude and
                                                              1
        phase reaches Port 1 of DUT. The reflected wave   moves back and is measured (in magnitude
                                                1
        and phase) by the power meter    connected through the directional coupler. The passing DUT
        signal   is measured the same way by the power meter    in the right branch of NA. Then the
              2
                                                                  ⁄
                                                   ⁄
        NA  internal computer calculates the ratios   11  =    and  21  =    at each  of swept
                                                  1
                                                                    1
                                                      1
                                                                 2
        frequency. Next, the internal RF switch is shifted to position 2 and all the measurements and
        calculations are reiterated producing the parameters   and  . Then the measured frequency
                                                         12
                                                   22
        dependable data are displayed in different formats like depicted in Figure 7.3.2a. If the DUT
        contains more than two ports, the described procedure should be repeated by consequently
        reconnecting each extra port to the port    at the front panel of NA while all remaining free
        DUT ports must be terminated in dummy loads. Evidently, NA must be carefully calibrated
        before any measurements to be sure that all power meters are synchronized in magnitude and
        phase. Moreover, in the process of calibration, all errors due to the imperfection of connectors,
        directional couplers, DUT cables, dummies, and many other NA elements should be taken into
        consideration by NA computer and compensated as much as possible. Have fun!
        7.3.3   Return and Insertion Loss
        The  measured or calculated  loss of power  due to reflection  from  DUT  is  called  Return
        (sometimes Reflection) Loss (RL) and expresses in decibels (dB) as

                                     ) = −10 log (| | ) = −20 log (| |)         (7.7)
                                                         2
                     = 10 log (  ⁄   10  11         10  11
                              10
        This quantity equal 0 dB causes full reflection while the values below 20 dB are considered as
        a good match. The similar definition characterizes the overall power loss in DUT. It is called
        Insertion Loss (IL) and also expresses in decibels (dB)
                                                          2
                              = 10 log (  ⁄   ) = −10 log (| | ) = −20 log (| |)        (7.8)
                              10                   10  21            10  21
                 is  the power delivered to the  dummy  load  behind the DUT.  Note that in  DUT
        Here  
        containing active elements like transistors, the reflected power may exceed the incident and RL
        becomes negative. The same is true for IL. If so, this parameter is customary called Gain (G)
        and G = -IL.

        In conclusion, note that the set of equations (7.6) should be naturally written in one of matrix
        form  that regards a passive electrical network  “…  as  a 'black box' containing  various


        1  Public  Domain Image, source:
        http://www.diytrade.com/china/pd/11596787/TD3618C_Vector_Network_Analyzer.html
        2  Public  Domain Image, source: http://www.ni.com/white-paper/11640/en/
   389   390   391   392   393   394   395   396   397   398   399