Page 455 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 455
6
453
System bus 1: RD+/TD+
Input Output 2: RD--/TD-- Block diagram of an input
3: TD--/RD--
4: TD+/RD+
5: GND Digital Input Supply
Housing: Shield X1 ... X8
M12 B coded
M12
M12
Diagnostics
M8
Digital Inputs 1: 24 V
X1 ... X8 3: 0 V U
LS
Logic
M8 Input 0 ... 7
4: Input
Error F
270 pF 270 pF
Supply 1: 24 V U
Input Output 2: 24 V U LS
3: 0 V U A Module
LS
4: 0 V U mount
A
M12 A coded
Technical Data Technical Data
Input characteristic: Isolation: 6
Input voltage Typical input current Channel – Channel No
0mA U LS , U A , system bus 500 V DC each
U IN
U IN - 5V 2.2 mA Configurable functions:
U IN - 11V 6.1 mA ... 6.3 mA Input filter (per channel) 0.1/ 0.5/ 3 /15 /20 ms/ filter off
-3 V < U IN < 0 V 7mA Inversion (per channel) On/off
System bus: Online simulation (per channel) Lock/unlock, simulation value: 0/1
Connection type (3) M12 connectors, B coded, 5 poles, Online simulation (per module) Diagnostics
shielded I/O diagnostics:
Standards and approvals: I/O diagnostics (per module) Short circuit/overload of sensor supply
Conformity marking 1 Undervoltage (U LS + U A )
Korea Certification Process image:
r UL 508 Process data width 1-byte data + status
LED indicators:
SB: System bus status LED (green/red/orange)
F: Error status LED (red)
0 ... 7: Input signal status LED (yellow)
U LS + U A : Supply status LED (green)
Indicators Non-latching
General Specifications
Dimensions (mm) W x H x L 50 x 35.7 x 117
Weight 270 g