Page 460 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 460
767-3806
6 Digital Input Module, 24 VDC, High Speed
458 8 inputs (4 x M12, two inputs per connector)
8DI HS
Module marking
System bus
output (3)
System bus
input (3)
6
LED indicators
X
4 4
X 7
3 Digital
inputs (2)
5 2
X
0 2
X 3 Channel marking
1
(2 fields per port/
1 field per channel)
1
Supply
24 V
U U output (1)
LS A
Supply 767-3806
input (1)
Short description: Included:
This digital input module records binary signals from sensors with short • 1 x WMB marker, yellow
response times. • 1 x marking strip
The 767-3806 Module features high-speed inputs, making it ideal for use with •2 x M12 protective cap
fast ETHERNET-based fieldbus systems (e.g., sercos).
Features:
• 8 digital inputs, 24 VDC
• Front-end cycle time (hardware) max. 6 μs
• Diagnostic-capable (module by module)
• Parametrizable (filter, inversion, online simulation and diagnostics)
Description Item No. Pack. Technical Data
Unit
8DI 24VDC HS (4xM12) 767-3806 1 Module supply:
Connection type (1) M12 connectors, A coded, 4 poles;
Derating must be observed
Current carrying capacity of supply
connections Max. 8 A (U LS : 4 A, U A : 4 A)
Supply voltage
24 V DC (-25 % ... +30 %)
Logic and sensor voltage U LS
24 V DC (-25 % ... +30 %);
Actuator voltage U A
Also required for power supply transmission
Supply current
typ. 45 mA + sensors (max. 1.0 A)
Logic and sensor current I LS
5 mA
Actuator current I A
Accessories Item No. Protection Reverse voltage protection for U LS + U A ;
short circuit protection for sensor supply
Marking strips, marking pen, spacer see pages 520 ... 521 Digital inputs:
module and protective caps Number of inputs 8
IP67 cables and connectors see pages 502 ... 517 + Section 11 Connection type (2) M12 connectors, A coded, 5 poles,
shielded
Wire connection 2- or 3-wire
Front-end cycle time (hardware) max. 6 μs
Front-end jitter/skew (input) < 2 μs
Input characteristic Type 3, acc. to IEC 61131-2
Signal voltage (0) -3 V ... +5 V DC
Signal voltage (1) +11 V ... +30 V DC
Input wiring high-side switching
Input voltage 24 VDC (-3 VDC < U IN < +30 VDC)
Input current (typ.) 2.8 mA
Connection of 2-wire BEROs max. 1.5 mA admissible closed current
Cable length, unshielded ≤ 30 m
Wrong connection of inputs No effect