Page 468 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 468
767-4804
6 Digital Output Module 24 V DC / 2.0 A
466 8 outputs (4 x M12, two outputs per connector)
8DO 2A
Module marking
System bus
output (3)
System bus
input (3)
6
LED indicators
X
4 4
X 7
3 Digital
outputs (2)
5 2
X
0 2 Channel
marking
X 3 (2 fields for
1 each port
1 field for
1
each channel)
24 V
U U
LS A Supply
Supply 767-4804 input (1)
input (1)
Short description: Included:
Digital output module for actuator control (e.g., magnetic valves, •Module WMB marker card, red (1 pcs)
DC contactors, indicators). • Marker strips (1 pcs)
• M8 protective caps (2 pcs)
Characteristics:
• 8 digital outputs DC 24 V / 2.0 A
• Diagnostic capable (per channel)
• Parametrizable (inversion, substitute value strategy,
manual mode, online simulation and diagnostics)
Description Item No. Pack. Technical Data
Unit
8DO 24V DC 2.0A (4xM12) 767-4804 1 Module supply:
8DO 24V DC 2.0A IF (4xM12)* 767-4804/000-800 1 Connection type (1) M12 connectors, A coded, 4 poles;
* Interference-free for safety function applications (see manual) Derating must be observed
Current carrying capacity of supply
connections Max. 8 A (U LS : 4 A, U A : 4 A)
Supply voltage
24 V DC (-25 % ... +30 %)
Logic and sensor voltage U LS
24 V DC (-25 % ... +30 %)
Actuator voltage U A
Supply current
typ. 45 mA (only logic part)
Logic and sensor current I LS
typ. 55 mA + actuators
Actuator current I A
Protection Reverse voltage protection for U LS + U A
Accessories Item No. Digital outputs:
No. of outputs 8
Marking strips, marking pen, spacer see pages 520 ... 521 Connection type (2) M12 connectors, A coded, 4 poles
module and protective caps Wire connection 2- or 3-wire
IP67 cables and connectors see pages 502 ... 517 + Section 11 Output voltage ≤ U A
Output current (per channel) 2.0 A (max. 2.4 A),
short-circuit/overload proof
(thermal disconnection)
Voltage drop against U A at 2.0 A Max. 0.2 V DC
Output current (module) max. 8 A
Leakage current in OFF state typ. 780 μA
Output circuit High-side switching