Page 472 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 472
767-4806
6 Digital Output Module 24 V DC / 0.5 A
470 8 outputs (4 x M12, two inputs per connector), low-side switching
8DO LS-S
Module marking
System bus
output (3)
System bus
input (3)
6
LED indicators
X
4 4
X 7
3 Digital
outputs (2)
5 2
X
0 2 Channel
marking
X 3 (2 fields for
1 each port
1 field for
1
each channel)
24 V
U U Supply
LS A
Supply 767-4806 outputs (1)
input (1)
Short description: Included:
Digital output module for actuator control (e.g., magnetic valves, • 1 x WMB marker, red
DC contactors, indicators). • 1 x marking strip
•2 x M12 protective cap
Features:
• 8 digital outputs, 24 V DC / 0.5 A, low-side switching
• Diagnostic capable (per channel)
• Parametrizable (inversion, substitute value strategy, manual mode,
online simulation and diagnostics)
Description Item No. Pack. Technical Data
Unit
8DO 24V DC 0.5A (4xM12) 767-4806 1 Module supply:
Connection type (1) M12 connectors, A coded, 4 poles;
Derating must be observed
Current carrying capacity of supply
connections Max. 8 A (U LS : 4 A, U A : 4 A)
Supply voltage
24 V DC (-25 % ... +30 %)
Logic and sensor voltage U LS
24 V DC (-25 % ... +30 %)
Actuator voltage U A
Supply current
Typ. 40 mA (only logic part)
Logic and sensor current I LS
Typ. 20 mA + actuators
Actuator current I A
Protection Reverse voltage protection for U LS + U A
Accessories Item No. Digital outputs:
No. of outputs 8
Marking strips, marking pen, spacer see pages 520 ... 521 Connection type (2) M12 connectors, A coded, 4 poles
module and protective caps Wire connection 2- or 3-wire
IP67 cables and connectors see pages 502 ... 517 + Section 11 Output voltage ≥ 0V U A
Output current (per channel) 0.5 A (max. 0.6 A),
short-circuit/overload protection
(thermal shutdown)
Voltage drop against U A at 500 mA Max. 0.2 V DC (0 V U A )
Output current (module) max. 4 A
Leakage current in OFF state typ. 150 μA
Output circuit Low-side switching