Page 475 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 475
6
473
System bus 1: RD+/TD+
Input Output 2: RD--/TD-- Block diagram of an output
3: TD--/RD--
4: TD+/RD+
5: GND Digital Output Supply
Housing: Shield X1 ... X8
M12 B coded
M12 M12
Digital Outputs 1: 24 V U A
X1 ... X8 3: 0 V U A
10 nF 10 nF
Logic
270 pF
M12 A coded
4: Output
2: n.c.
Output Error
Supply 1: 24 V U 0 ... 7 F
Input Output 2: 24 V U LS Module
mount
3: 0 V U A
4: 0 V U LS
A
M12 A coded
Technical Data Technical Data
Information on actuator selection: Isolation: 6
Delay time hardware from "0" to "1" Channel – Channel no
(0 – 90%) typ. 65 μs (resistive load) U LS , U A , system bus 500 V DC each
Delay time hardware from "1" to "0" Configurable functions:
(0 – 90%) typ. 190 μs (resistive load) Inversion (per channel) On/off
Rise time from "0" to "1" typ. 40 μs (resistive load) Substitute value strategy (per channel) Switch substitute value/hold last value
Fall time from "1" to "0" typ. 50 μs (resistive load) Substitute value (per channel) 0/1
Cable length, unshielded ≤ 30 m Manual mode (per channel) On/off
Protection against reverse voltages ≤ 0.5 A Manual mode value (per channel) 0/1
Type of load Inductive, resistive loads and lamps Online simulation (per channel) Lock/unlock; simulation value: 0/1
Switching frequency Inductive load approx. 20 Hz Online simulation (per channel/
Resistive load approx. 500 Hz module) Diagnostics
Lamp load approx. 500 Hz I/O diagnostics:
Parallel connection of 2 outputs for power boost I/O diagnostics (per channel) Actuator short-circuit/overload
for redundant actuation of a load Actuator wire break
Type of protective circuit External protection (e.g., recovery diodes) Overtemperature
Output resistance < 0.4 Ω I/O diagnostics (per module) Undervoltage (U LS + U A )
Operating state influence on output: Process image:
PLC CPU stop Acc. to substitute value strategy Process data width 1-byte data + status
Fieldbus disruption Acc. to substitute value strategy LED indicators:
S-bus (system bus) disruption 0 V status SB: System bus status LED (green/red/orange)
Supply voltage under rated voltage F: Error status LED (red)
tolerance 0 V status 0 ... 7: Output signal status LED (yellow/red)
Interruption of supply voltage 0 V status U LS + U A : Supply status LED (green)
Output operation Non-latching Indicators Non-latching
Overload behavior Automatic restart
System bus:
Connection type (3) M12 connectors, B coded, 5 poles,
shielded
Standards and approvals:
Conformity marking 1
Korea Certification
r UL 508
General Specifications
Dimensions (mm) W x H x L 50 x 35.7 x 170
Weight 385 g