Page 471 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 471

6

                                                                                                                    469


                    System bus   1: RD+/TD+
                 Input                Output  2: RD--/TD--                      Block diagram of an output
                                 3: TD--/RD--
                                 4: TD+/RD+
                                 5: GND                             Digital Output                     Supply
                                 Housing: Shield                    X1 ... X8
                       M12 B coded
                                                                    M8                                  M12

                    Digital Output  1: 24 V U
                      X1 ... X8  3: 0 V U  A
                                     A
                                                                                                     10 nF  10 nF
                                                                                               Logic
                                                                        270 pF
                          M8
                                 4: Output

                                                                                         Output 0 ... 7  Error F
                     Supply      1: 24 V U                                                              Module
                        Input            Output  2: 24 V U LS                                            mount
                                 3: 0 V U  A
                                     LS
                                 4: 0 V U
                                     A
                       M12 A coded





           Technical Data                                       Technical Data
           Information on actuator selection:                   Isolation:                                          6
            Delay time hardware from "0" to "1"                   Channel – Channel       No
            (0 – 90%)               Typ. 75 μs (resistive load)   U LS , U A , system bus  500 V DC each
            Delay time hardware from "1" to "0"                 Configurable functions:
            (0 – 90%)               Typ. 270 μs (resistive load)  Inversion (per channel)  On/off
            Rise time from "0" to "1"  Typ. 150 μs (resistive load)  Substitute value strategy (per channel)  Switch substitute value / hold last value
            Fall time from "1" to "0"  Typ. 150 μs (resistive load)  Substitute value (per channel)  0/1
            Cable length, unshielded  ≤ 30 m                      Manual mode (per channel)  On/off
            Protection against reverse voltages  ≤ 0.5 A          Manual mode value (per channel)  0/1
            Type of load            Inductive, resistive loads and lamps  Online simulation (per channel)  Lock/unlock; simulation value: 0/1
            Switching frequency     Inductive load approx. 20 Hz   Online simulation (per channel/
                                    Resistive load approx. 500 Hz   module)               Diagnostics
                                    Lamp load approx. 500 Hz    I/O diagnostics:
            Parallel connection of 2 outputs  For power boost     I/O diagnostics (per channel)  Overtemperature
                                    For redundant load actuation  I/O diagnostics (per module)  Undervoltage (U LS  + U A )
            Type of protective circuit  External protection (e.g., recovery diodes)  Process image:
            Output resistance       < 0.4 Ω                       Process data width      1-byte data + status
           Operating state influence on output:                 LED indicators:
            PLC CPU stop            Acc. to substitute value strategy  SB: System bus status  LED (green/red/orange)
            Fieldbus disruption     Acc. to substitute value strategy  F: Error status    LED (red)
            S-bus (system bus) disruption  0 V status             0 ... 7: Output signal status  LED (yellow/red)
            Supply voltage under rated voltage                    U LS  + U A : Supply status  LED (green)
            tolerance               0 V status                    Indicators              Non-latching
            Interruption of supply voltage  0 V status
            Output operation        Non-latching
            Overload behavior       Automatic restart
           System bus:
            Connection type (3)     M12 connectors, B coded, 5 poles,
                                    shielded
           Standards and approvals:
            Conformity marking      1
            Korea Certification
            r UL 508



                                                                General Specifications
                                                                Dimensions (mm) W x H x L  50 x 35.7 x 117
                                                                Weight                    270 g