Page 476 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 476

767-4808

   6    Digital Output Module, 24 VDC, 0.1 A, High Speed

  474   8 outputs (4 x M12, two outputs per connector)


                                                                                     8DO HS
                                                          Module marking
                                                                                             System bus
                                                                                             output (3)
                                                               System bus
                                                                input (3)
                                                                                     6
                                                             LED indicators
                                                                                          X
                                                                              4           4
                                                                        X            7
                                                                        3                    Digital
                                                                                             outputs (2)
                                                                              5      2
                                                                                          X
                                                                              0           2
                                                                        X            3       Channel marking
                                                                        1
                                                                                             (2 fields per port/
                                                                              1              1 field per channel)
                                                                                             Supply
                                                                                24 V
                                                                                U  U         output (1)
                                                                                 LS  A
                                                                 Supply        767-4808
                                                                input (1)



        Short description:                                  Included:
        This digital output module outputs signals from actuators with short response   • 1 x WMB marker, red
        times. The 767-4808 Module features high-speed outputs, making it ideal for   • 1 x marking strip
        use with fast ETHERNET-based fieldbus systems (e.g., sercos).  •2 x M12 protective cap

        Features:
        • 8 digital outputs, 24 VDC / 0.1 A
        • Front-end cycle time (hardware) max. 0,5 μs
        • Diagnostic-capable (channel by channel/module by module)
        • Parametrizable (inversion, substitute value strategy, substitute value,
          manual mode, online simulation and diagnostics)


        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        8DO 24VDC 0,1A HS (4xM12)    767-4808        1        Module supply:
                                                                Connection type (1)    M12 connectors, A coded, 4 poles;
                                                                                       Derating must be observed
                                                                Current carrying capacity of supply
                                                                connections            Max. 8 A (U LS : 4 A, U A : 4 A)
                                                                Supply voltage
                                                                                       24 V DC (-25 % ... +30 %)
                                                                 Logic and sensor voltage U LS
                                                                                       24 V DC (-25 % ... +30 %)
                                                                 Actuator voltage U A
                                                                Supply current
                                                                                       typ. 40 mA (logic component only)
                                                                 Logic and sensor current I LS
                                                                                       typ. 35 mA + actuator supply (≤ 1 A) +
                                                                 Actuator current I A
                                                                                       load
        Accessories                  Item No.                   Protection             Reverse voltage protection for U LS  + U A ,
                                                                                       short-circuit protection for actuator supply
        Marking strips, marking pen, spacer   see pages 520 ... 521  Digital outputs:
        module and protective caps                              No. of outputs         8
        IP67 cables and connectors   see pages 502 ... 517 + Section 11  Connection type (2)  M12 connectors, A coded, 5 poles,
                                                                                       shielded
                                                                Wire connection        2- or 3-wire
                                                                Output voltage         ≤ U A
                                                                Output current (per channel)  0.1 A,
                                                                                       short-circuit/overload proof
                                                                                       (thermal disconnection)
                                                                Voltage drop against U A  at 500 mA  Max. 1.7 V DC
                                                                Output current (module)  max. 0.8 A
                                                                Leakage current in OFF state  typ. 50 μA
                                                                Output circuit         Push/Pull
   471   472   473   474   475   476   477   478   479   480   481