Page 481 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 481

6

                                                                                                                    479







                      System bus    1: RD+/TD+
                      Input           Output  2: RD--/TD--                     Block diagram of an input/output
                                    3: TD--/RD--
                                    4: TD+/RD+
                                    5: GND                          Digital Input/Output                Supply
                                    Housing: Shield                 X1 ... X4
                        M12, B coded
                                                                     M12                                 M12
                                                                                                          2
                                                                      3              Diagnostics sensor/actuator supply  4
                  Digital Inputs/Outputs
                       X1 ... X4  1: 24 V
                                                                      1
                  (two channels per connector) 3: 0 V U A
                                                                                          Input 0 ... 7
                                                                                                      10 nF  10 nF
                                                                                                Logic
                                                                                          Output 0 ...7
                                                                      4/2
                        M12, A coded
                                  4: In-/Output A
                                  2: In-/Output B
                                                                                           Input/Output  Error
                                                                                             0 ... 7  F
                       Supply       1: 24 V U                           10 nF  270 pF
                     Input                 Output  2: 24 V U LS
                                         A
                                    3: 0 V U LS
                                    4: 0 V U
                                        A
                                                                                                         Module
                                                                                                          mount
                        M12, A coded
           Technical Data                                       Technical Data
           Digital outputs:                                     Counters:                                           6
            No. of outputs          8                             No. of counters         2
            Connection type (2)     M12 connectors, A coded, 4 poles  Counter type        Event/Gate time counter, pulse duration
            Wire connection         2- or 3-wire                  Counting/switching frequency  0 Hz ... 1 kHz
            Output voltage          ≤ U A                       System bus:
            Output current (per channel)  0.5 A (max. 0.6 A),     Connection type (3)     M12 connectors, B coded, 5 poles,
                                    short-circuit/overload proof                          shielded
                                    (thermal disconnection)     Standards and approvals:
            Voltage drop against U A  at 500 mA  max. 0.2 V DC    Conformity marking      1
            Output current (module)  max. 4 A                     Korea Certification
            Leakage current in OFF state  typ. 5 μA               r UL 508
            Output circuit          High-side switching         Isolation:
           Information on actuator selection:                     Channel – Channel       no
            Delay time hardware from "0" to "1"                   U LS , U A , system bus  500 V DC each
            (0 – 90%)               typ. 90 μs (resistive load)  Configurable functions:
            Delay time hardware from "1" to "0"                   Operating mode (per module)  DO-Module/DI-Module/DIO-Module/
            (0 – 90%)               typ. 310 μs (resistive load)                          DIO + 1 counter/DIO + 2 counters
            Rise time from "0" to "1"  typ. 60 μs (resistive load)  Input filter (per channel)  0.1/ 0.5/ 3 /15 /20 ms/ filter off
            Fall time from "1" to "0"  typ. 45 μs (resistive load)  Inversion (per channel)  On/off
            Cable length, unshielded  ≤ 30 m                      Substitute value strategy (per channel)  Switch substitute value/hold last value
            Reverse current (in case of recovery for              Substitute value (per channel)  0/1
            voltages > U A )        ≤ 0,5 A (error: 1 channel)    Manual mode (per channel)  On/off
            Type of load            Inductive, resistive loads and lamps  Manual mode value (per channel)  0/1
            Switching frequency     Inductive load approx. 20 Hz   Online simulation (per channel)  Lock/unlock; simulation value: 0/1
                                    Resistive load approx. 500 Hz   Online simulation (per channel/module)  Diagnostics
                                    Lamp load approx. 500 Hz    I/O diagnostics:
            Parallel connection of 2 outputs  for power boost     I/O diagnostics (per channel)  Overtemperature
                                    for redundant actuation of a load  I/O diagnostics (per module)  Sensor/Actuator supply short-circuit/
            Type of protective circuit  External protection (e.g., recovery diodes)       overload; Undervoltage (U LS  + U A )
            Output resistance       < 0.4 Ω                     Process image:
           Operating state influence on output:                   Process data width      Depends on operating mode
            PLC CPU stop            Acc. to substitute value strategy  LED indicators:
            Fieldbus disruption     Acc. to substitute value strategy  SB: System bus status  LED (green/red/orange)
            S-bus (system bus) disruption  0 V status             F: Error status         LED (red)
            Supply voltage under rated voltage                    0 ... 7: Input and output signal status  LED (yellow)
            tolerance               0 V status                    0 ... 7: Output diagnostics  LED (red)
            Interruption of supply voltage  0 V status            U LS  + U A : Supply status  LED (green)
            Output operation        Non-latching                  Indicators              Non-latching
            Overload behavior       Automatic restart           General Specifications

                                                                Dimensions (mm) W x H x L  50 x 35.7 x 117
                                                                Weight                    255 g
   476   477   478   479   480   481   482   483   484   485   486