Page 484 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 484
767-5401
6 Digital Input/Output Module, 24 VDC / 0.2 A, High Speed
482 4 inputs/outputs (4 x M12)
4DIO HS
Module marking
System bus
output (3)
System bus
input (3)
3
LED indicators
X
2 4
X
3 Digital inputs /
outputs (2)
1
X
0 2
X Channel marking
1
(2 fields per
port/channel)
Supply
24 V
U U output (1)
LS A
Supply 767-5401
input (1)
Short description: Included:
This digital input/output module records/outputs binary signals from • 1 x WMB marker, orange
sensors/actuators with short response times. The 767-5401 Module • 1 x marking strip
features high-speed inputs/outputs, making it ideal for use with fast ETHERNET- •2 x M12 protective cap
based fieldbus systems (e.g., sercos).
Features:
• 4 digital inputs/outputs, 24 VDC / 0.2 A, incl. counter function
• Front-end cycle time (hardware) max. 3 μs
• Diagnostic-capable (channel by channel/module by module)
• Parametrizable (operating mode, filter, inversion, substitute value strategy,
substitute value, manual mode, online simulation and diagnostics)
Description Item No. Pack. Technical Data
Unit
4DIO 24VDC 0.2A HS (4xM12) 767-5401 1 Digital inputs:
Number of inputs 4
Connection type (2) M12 connectors, A coded, 5 poles,
shielded
Accessories Item No. Wire connection 2- or 3-wire
Front-end cycle time (hardware) max. 3 μs
Marking strips, marking pen, spacer see pages 520 ... 521 Front-end jitter/skew (input) < 2 μs
module and protective caps Input characteristic Type 1, acc. to IEC 61131-2
IP67 cables and connectors see pages 502 ... 517 + Section 11 Signal voltage (0) -3 V ... +5 V DC
Signal voltage (1) +15 V ... +30 V DC
Technical Data Input wiring high-side switching
Input voltage 24 VDC (-3 VDC < U IN < +30 VDC); Power
Module supply: from U A strongly recommended
Connection type (1) M12 connectors, A coded, 4 poles; Input current (typ.) 2.9 mA
Derating must be observed Connection of 2-wire BEROs max. 1.5 mA admissible closed current
Current carrying capacity of supply Wrong connection of inputs No effect
connections Max. 8 A (U LS : 4 A, U A : 4 A) Cable length, shielded ≤ 30 m
Supply voltage Input characteristic:
24 V DC (-25 % ... +30 %) Input voltage Typical input current
Logic and sensor voltage U LS
24 V DC (-25 % ... +30 %) 0 V 0 mA
Actuator voltage U A
Supply current 5 V 2.0 mA
typ. 40 mA (logic component only) 15 V 2.5 mA
Logic and sensor current I LS
typ. 30 mA + sensors/actuators 24 V 2.9 mA
Actuator current I A
(max. 1000 mA) + load 30 V 3.2 mA
Protection Reverse voltage protection for U LS + U A
Short-circuit protection for sensor/actuator
supply