Page 485 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 485
6
483
System bus 1: RD+/TD+
Input Output 2: RD--/TD-- Block diagram of an input/output
3: TD--/RD--
4: TD+/RD+
5: GND Digital Input/Output Supply
Housing: Shield X1 ... X4
M12, B coded
M12 M12
2
3 Diagnostics sensor/actuator supply 4
Digital Inputs/Outputs
X1 ... X4 1: 24 V
3: 0 V U 1
A Input 0 ... 3
10 nF 10 nF
Logic
5 5
5: Shield
Output 0 ... 3
4
M12, A coded
4: In-/Output
Housing: Shield
Input/Output Error
0 ... 3 F
270 pF 270 pF
Supply 1: 24 V U
Input Output 2: 24 V U LS
3: 0 V U A 5
4: 0 V U LS
A
Module
mount
M12, A coded
Technical Data Technical Data
Digital outputs: Counters: 6
No. of outputs 4 No. of counters 1
Connection type (2) M12 connectors, A coded, 5 poles, Counter type Event, gateway time, pulse duration
shielded Counting/switching frequency 0 Hz ... 1 kHz
Wire connection 2- or 3-wire System bus:
Output voltage ≤ U A Connection type (3) M12 connectors, B coded, 5 poles,
Output current (per channel) 0.2 A, shielded
short-circuit/overload proof Standards and approvals:
(thermal disconnection) Conformity marking 1
Voltage drop against UA at 200 mA Max. 2.0 V DC r UL 508
Output current (module) max. 0.8 A Isolation:
Leakage current in OFF state typ. 100 μA Channel – Channel No
Output circuit Push/Push U LS , U A , system bus 500 VDC each
Information on actuator selection: Configurable functions:
Front-end cycle time 90% (hardware) max. 0,5 μs Operating mode (per module) DO module/DI module/DIO module/
Edge steepness T ON/OFF : typ. < 0,2 μs DIO + 1 counter
Front-end jitter/skew (output) < 0,2 μs Input filter (per channel) 10/ 25/ 50/ 100/ 200 μs/ 1/ 3 ms/
Type of load Inductive, resistive loads and lamps filter off
Switching frequency Inductive load upon request Inversion (per channel) On/off
Resistive load upon request Substitute value strategy (per channel) Switch substitute value/hold last value
Lamp load upon request Substitute value (per channel) 0/1
Type of protective circuit External protection (e.g., recovery diodes) Manual mode (per channel) On/off
Operating state influence on output: Manual mode value (per channel) 0/1
PLC CPU stop Acc. to substitute value strategy Online simulation (per channel) Lock/unlock, simulation value: 0/1
Fieldbus disruption Acc. to substitute value strategy Online simulation (per channel/module) Diagnostics
S-bus (system bus) disruption 0 V status I/O diagnostics:
Supply voltage under rated voltage I/O diagnostics (per channel) Overtemperature
tolerance 0 V status I/O diagnostics (per module) Short-circuit of sensor/actuator supply
Interruption of supply voltage 0 V status Undervoltage (U LS + U A )
Output operation Non-latching Process image:
Overload behavior Automatic restart Process data width depends on operating mode
LED indicators:
SB: System bus status LED (green/red/orange)
F: Error status LED (red)
0 – 3: Signal status, inputs/outputs LED (yellow/red)
0 – 3: Diagnostics, outputs LED (red)
U LS + U A : Supply status LED (green)
Indicators Non-latching
General Specifications
Dimensions (mm) W x H x L 50 x 35.7 x 117
Weight 255 g