Page 490 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 490
767-6403
6 Analog Input Module for Thermocouples (TCs)
488 4 inputs
4AI TC
Module marking
System bus
output (3)
System bus
input (3)
Ch4
LED indicators
X
Ch3 4
X Er4
3 Analog
input (2)
Ch2
Er3
X
Ch1 2
X Er2 Channel
1 marking
(2 fields for each
Er1
port/channel)
Supply
24 V
U U outputs (1)
LS A
Supply 767-6403
input (1)
Short description: Included:
This analog input module receives the measured values from thermocouples • WMB module marker card, green
and voltage sensors. •Marker strip
• M12 protective caps (2 pcs)
Characteristics:
• 4 analog inputs TC*
• Diagnostic capable
• Parametrizable (measuring range, limiting values, filter, cold junction
compensation, substitute value, online simulation and diagnostics)
* Preassembled connector for cold junction compensation available as accessory.
Description Item No. Pack. Technical Data
Unit
4AI TC 767-6403 1 Module supply:
Connection type (1) M12 connectors, A coded, 4 poles;
Derating must be observed
Current carrying capacity of supply
connections Max. 8 A (U LS : 4 A, U A : 4 A)
Supply voltage
24 V DC (-25 % ... +30 %)
Logic and sensor voltage U LS
24 V DC (-25 % ... +30 %);
Actuator voltage U A
Also required for power supply transmission
Supply current
Typ. 40 mA
Logic and sensor current I LS
≤ 5mA
Actuator current I A
Accessories Item No. Protection Reverse voltage protection for U LS + U A
Analog inputs:
Marking strips, marking pen, spacer see pages 520 ... 521 Number of inputs 4
module and protective caps Connection type (2) M12 connectors, A coded, 5 poles
IP67 cables and connectors see pages 502 ... 517 + Section 11 Type of signal Thermocouple and low voltages
Compensation connector, 756-9207/050-000 Wire connection 2-wire
M12 plug, straight, spring clamp (external shield (screen)
technology via knurled nut)